The following configuration must be done in the PBHIOMB blocks.
• PDC Name Reference must be associated to a PDC defined in the DSB block to obtain the following
information about the PDC.
– Slave Address
– PDC Number
– PDC Description
– PDC Grouped
– Channel Number Offset
– Number of channels
Attention
The Number of Channels parameter can be configured only when the PDCs are grouped.
– Slot Type
• Slot Number must be configured to identify the module position in the chassis.
Note
DSB blocks must be configured for configuring the PDC Name Reference in the PBHIOMB block. The maximum
number of PBHIOMB supported for one PBLINK is 256 considering that a minimum of one HART device is
connected to each PBHIOMB. Hence, the number of PBHIOMB supported on both the links is 512.
Bulk Build support for PBHIOMB block
When you create a bulk build of the PBHIOMB block, you must configure the ASSIGNEDDSBNAME
parameter in the excel sheet to which the PBHIOMB needs to be associated. In addition, you must configure the
protocol block-related information in the excel sheet to which the DSB is associated.
For more information about the ASSIGNEDDSBNAME parameter, see
Control Builder Parameter Reference
.
8.1.1 PBHIOMB block creation
A PBHIOMB block is created by dragging a PBHIOMB module template from the Library and assigning it to
the DSB block in the Project view.
You can also create a PBHIOMB block from the
File
menu. (
File
>
New
>
I/O Modules
>
PGM_IF
>
PBHIOMB – Profibus HART I/O Module Block
). In this method, the PBHIOMB block is created under the
“Unassigned” blocks. You must drag and drop the PBHIOMB block to the DSB block.
8.1.2 PBHIOMB block deletion
The PBHIOMB block can be deleted from the Project view in Control Builder even if the PBHCHANNEL is
configured. To delete the PBHIOMB block either from the Project view or Monitoring view, right-click the
PBHIOMB block and then click
Delete
.
Attention
THe PBHCAHNNELs configured under the PBHIOMB block are also deleted when the PBHIOMB block is deleted.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
189
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...