8.4 Configuring a PBHIOMB block
Prerequisites
• DSB for the PROFIBUS slave module is created and configured.
• HART Device Description (DD)-based template is already created in the Library.
• PDC grouping can be performed in the DSB, as applicable.
Attention
If you configure the PBHIOMB for universal modules, then you must need more than one PBHIOMB blocks since the
universal modules contain configurable channels, which can be configured as Analog Input or Analog Output. For
example, if a universal module contains eight channels, then the first two channels can be configured as “Analog input
channels” and the remaining six channels can be configured as “Analog output channels.”
To configure a PBHIOMB block when PDC is not grouped
1
Click
File
>
New
>
I/O Modules
>
PGM_IF
> PBHIOMB.
When you create a PBHIOMB, it resides in the
Unassigned
folder in the Project tree. You must drag-and-
drop it to the DSB.
2
(Optional) Perform the following steps.
a
Drag-and-drop the PBHIOMB from the PGM_IF library to the DSB that is assigned to a PBLINK.
The
Name New Function Blocks
dialog box appears.
b
In the
Destination
column, you can accept the default name or modify the name, if required and then
click
Finish
.
The PBHIOMB block appears under the DSB block.
3
Double-click the PBHIOMB.
The PBHIOMB block configuration form appears.
4
In the
Tag Name
box, type the name of the PBHIOMB (a maximum of 16 characters) or accept the default.
5
In the
Item Name
box, type the item name.
6
In the
Description (DESC)
box, type a brief description of up to 132 characters.
7
Click the point picker to configure the
PDC Name Reference (PDCNAMEREF)
and then select the
associated HART-enabled device that is configured in the DSB block.
Attention
•
The
PDC Name Reference
parameter can be configured only if the PBHIOMB is assigned to the DSB.
•
Only PDCs of the DSB to which the PBHIOMB block is associated are listed in the point picker dialog box.
•
The PBHIOMB can be associated only to the following DSBs that follows the RIO profile.
– GENDSB
– GENIODSB
– TURCKEXCOM
– CEAGDSB
– ET200MDSB
Once the PDCNAMEREF is selected the following parameters are updated automatically.
• Slave Name (SLAVENAME)
• Slave Address (SLAVEADDRESS)
• Slot Type (SLOTTYPE)
• PDC Description (PDCDESCRIPTION)
• PDC Number
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
193
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...