Alarm
Description
Not Synchronized
This alarm is reported when the primary and secondary PGM are not
synchronized or not in standby.
The "Not Synchronized" alarm returns to normal upon configuring the
primary at the odd device Index or upon entering the Synchronized or
Standby state.
Unexpected Partner on Redundancy Link
This alarm is reported when the PGM is explicitly configured as non-
redundant and a partner is present on the redundancy private path.
The RDNSYNCSTATE parameter is set to either PARTNERVISBL or
INCOMPATIBLE.
This alarm returns to normal after the PGM is re-configured as
redundant or if the partner is removed from the redundancy link.
Device Index Switches Changed
This alarm is reported when the device index of the PGM is changed
when it is up and running. In such a scenario, the PGM retains the
device index value assumed at start up.
The alarm returns to normal after the device index is changed to its
original number.
Note:
Changing the device index number does not affect the control
strategies and there is no loss of data. However, a soft fail is generated.
Attention
If the PGM is powered off and on, the PGM clears it memory
database and also clears the device index value.
Duplicate Device Index alarm
This alarm is reported when the device index of the secondary PGM is
identical to the device index of another node.
FTE A/B cable Fault Alarm
This alarm is reported when one of the FTE cables (FTE-A/FTE-B) is
removed or is faulty. This alarm returns to normal when the FTE cable
is reconnected. In such a scenario, PGM will be up and running. Also,
the control strategies do not lose the data from the PGM.
Attention
Note that the PGM can operate with a single FTE.
OFFNET
This alarm is reported when both the FTE cables are removed. In such
a scenario, there is a loss of view of the PGM block. The control
strategies lose data from the PGM.
This alarm returns to normal if one of the FTE cables is re-connected.
When re-connected, the control strategies start receiving data from the
PGM.
Temperature High Alarm
This alarm is reported when the temperature high alarm set point value
reaches lower than the specified set point.
5 PROFIBUS GATEWAY MODULE (PGM) BLOCK
41
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...