4
Type the value
6000
in the
Data Control Time
box.
5
Select the
Override slave specific Watchdog Control Time
check box.
6
Type the value
1000
in the
Watchdog Control Time
box.
Attention
•
The Watchdog control time and Data control time must have proper values based on the number of slave
devices configured in the network and the bus speed. In addition, V1 communication has a major impact on
the watchdog data control time values . If DP-V1 is enabled for a slave device, the Watchdog control time and
Data control times must be about three times longer than the actual time when DP-V1 is disabled.
•
By default, the ET200M devices have DP-V1 enabled.
The following table lists the recommended baud rates and their corresponding Watchdog Control Time and
Data Control Time.
Baud Rate
Watchdog Control Time
Data Control Time
1500
1000
6000
500
1000
6000
187.5
2000
12000
93.75
3000
18000
45.45
4000
24000
19.2
5000
30000
9.6
6000
36000
7
Click
Apply
.
8
Click
OK
.
9
Click
Save
in the
Field Network Configuration
tab toolbar.
A message appears after you save the configuration.
5 PROFIBUS GATEWAY MODULE (PGM) BLOCK
45
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...