5.6.6 PGM redundancy notifications
The following table lists the redundancy-related notifications implemented for the PGM that may occur during
controller synchronization and switchover operations.
Notification
Generated when…
Backup State
The secondary PGM is successfully restarted.
Redun Incompatible Partner
The redundancy cable of the primary PGM is connected to a different PGM.
Redun No Partner
Both the primary and the secondary PGM generate this notification when the partner is not
present.
Redun Non-Redundant
Both FTE cables of the PGM configured explicitly as non-redundant are removed and re-
connected after sometime.
Redun Partner Visible on
FTE
Both FTE cables of the secondary PGM are removed and re-connected after sometime.
Redun Partner Visible on
Redun Link
Both the primary and the secondary PGM generate this notification upon detecting a
compatible partner visible across the redundancy private path.
Redun Sync In Progress
Both the primary and the secondary PGM generate this notification after both FTE cables
are removed and re-connected and the initial synchronization is started.
Redun Sync Maintenance
Both the primary and the secondary PGM generate this notification after completing the
initial synchronization.
Redundancy Link Active
This notification is generated when the redundancy link cable is connected.
Redundancy Link Inactive
This notification is generated when the redundancy link cable is disconnected.
Switchover
Both the primary and the secondary PGM generate this notification when a switchover is
initiated by entering the switchover command.
5 PROFIBUS GATEWAY MODULE (PGM) BLOCK
47
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...