EP03-300-200
December,
2003
Release 200
Version 1.0
Experion PKS CEE-based Controller Specifications and Models
31
Table 17. Typical IOM/CM/SCM Processing and Memory Resource Requirements
Processing Resource Consumption Memory Resource
Consumption
Typical Module Types
(FB Content in Parentheses)
Total Processing Consumption (PU/sec) per module type =
Processing Resource Consumption (PU/module execution) /
Execution Period (sec/module execution) * number of Modules
50/5 ms CEE
Non-Redundant
(PU/Module
Execution)
50 ms CEE
Redundant
(PU/Module
Execution)
500 ms ACE
50/5 ms CPM
CEE (Mu/Mod)
Typical I/O Module
(Average consumption of available IOM’s)
0.3 0.19 0.6
Analog Data Acquisition CM
(10 AI, 10 DataAcq FB’s)
2.9 3.8 7.4
Small Analog Data Acquisition CM
(1 AI, 1 DataAcq FB’s)
0.47 0.43 1.0
Regulatory Control CM
(1 AI, 1 DataAcq, 1 PID, 1 AO, 6 Logic FB’s)
2.8 2.8 3.9
PID-PL Regulatory Control CM
1
(1 AI, 1 DataAcq, 1 PID-PL, 1 AO, 6 Logic FB’s)
4.2
2
4.2
2
5.1
2
Auxiliary Function CM
(10 Aux. FB’s, such as AuxCalc, Totalizer)
4.2 5.1 13.1
Digital Data Acquisition CM
(10 DI, 10 Flag FB’s)
1.2 1.2 3.1
Small Digital Data Acquisition CM
(1 DI, 1 Flag FB’s)
0.22 0.14 0.6
Device Control CM
(2 DI, 2 DO, 1 DevCtl, 5 Logic FB’s)
1.3 1.3 3.1
Logic Control CM
(20 Logic FB’s)
1.0 1.0 3.5
Sequence Control Module (SCM) A
(Includes: 1 handler of each: Main, Hold, Stop and Abort; a total of
10 Steps with 8 Outputs and a total of 10 Transitions with 5
Conditions spread over all handles; 10 Recipe items, 5 History
items)
Total of 10 Steps and 10 Transitions spread over the 4 Handlers
2.0 3.0 28.9
Sequence Control Module (SCM) B
(Includes: 1 Main Handler, no other Handlers, 20 Steps with 4
Outputs each, 20 Transitions with 3 Conditions each, 10 Recipe
items, 5 History Items)
Total of 20 Steps and 20 Transitions
2.0 3.0 35.7
Sequence Control Module with an alias table of size
45 rows by 100 columns
(Includes: 1 handler of each: Main, Hold, Stop and Abort; a total of
10 Steps with 8 Outputs and a total of 10 Transitions with 5
Conditions spread over all handlers, 10 Recipe items, 5 History
items)
Total of 10 Steps and 10 Transitions spread over the 4 Handlers
2.0 3.0
128.5
Sequence Control Module with an alias table of size
500 rows by 9 columns
(Includes: 1 handler of each: Main, Hold, Stop and Abort, a total of
10 Steps with 8 Outputs and a total of 10 Transitions with 5
Conditions spread over all handlers, 10 Recipe items, 5 History
items)
Total of 10 Steps and 10 Transitions spread over the 4 Handlers
2.0 3.0
124.5
The following Function Block libraries consume the following extra
memory when the first block is loaded to the C200 Controller:
S
Allen-Bradley Drive – 90 Mus
S
AGA Calculation – 172 Mus
S
DeviceNet Interface – 106 MUs
S
Exchange (PLC5 & Logix5550) – 89 MUs
S
Pulse Input IOM – 90 MUs
S
FBUSIF (Linking Device) – 82 Mus
S
HART I/O – 105 Mus
S
Profibus Interface – 244 Mus
S
Rail (RIOM- H) I/O – 107 MUs
S
Rail (RIOM- A) I/O – 120 MUs
1
The PID-PL block supports execution rates as fast as 50ms for ACE and C200. A CM with the PID-PL block consumes
approximately 50 percent more PUs as compared to a CM with the standard PID block. A CM with the PID-PL block utilizes
circa 30 percent more MUs as compared to a CM with the standard PID block.
2
Estimated value