7.7 CEAG Device Support Block (CEAGDSB)
The CEAGDSB runs on the PGM and represents one PROFIBUS field device in the PROFIBUS network. The
CEAGDSB processes the raw data from the CEAG field devices and converts it to the PDC format supported
by Experion. The CEAGDSB communicates with the master PGM for data conversion.
A single CEAGDSB supports up to 46 I/O modules. The CEAGDSB is used for configuring the CEAG LB/FB
Remote I/O family when using PROFIBUS communication unit Easy COM LB8106/FB8206 V6.XX.
The CEAGDSB supports the I/O stations per bus line that provide 31 stations without repeaters and up to 125
stations with repeaters. The maximum number of modules per slave device is 49 (46 I/O modules plus 3 slots
reserved for the communication unit) in the field network configuration. The communication unit present in
each station transfers the data of internal system bus to the protocols of the master bus system.
The maximum number of PDCs required per station is 48 and this can be interpreted as follows:
• 2 PDCs for the communication unit and 46 PDCs for 46 one-channel modules.
Or
• 2 PDCs for the communication unit and 46 PDCs for 23 multi-channel modules having both inputs and
outputs.
Attention
•
The maximum number of one-channel I/O module per station is 46.
•
The maximum number of multi-channel I/O module per station is 23.
Related topics
“Device Support Block (DSB) overview” on page 112
“Generic Drive Device Support Block (DRIVEDSB)” on page 124
“Generic Device Support Blocks (GENPADSB and GENPAGWDSB) for PA devices” on page 122
“Siemens AS-i Link Device Support Block (Siemens DP/AS-i-Link DSB)” on page 134
“Siemens ET200M Device Support Block (Siemens ET200M DSB)” on page 138
“Turck Excom Device Support Block (Turck Excom DSB)” on page 142
“Generic Device Support Blocks (GENDSB and GENIODSB)” on page 120
7.7.1 I/O modules supported by the CEAGDSB
The following tables lists the I/O modules supported by the CEAGDSB.
CEAGDSB
PDC Type
Supported CEAG modules
Digital Input with line fault detection - 2 channels
•
LB1101
•
LB1001
•
FB1201
•
FB1301
Digital Input with line fault detection - 3 channels
•
LB1102
•
LB1002
•
FB1202
•
FB1302
•
2xxx
7 DEVICE SUPPORT BLOCK (DSB)
129
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...