7.9 Siemens ET200M Device Support Block (Siemens ET200M DSB)
The Siemens ET200M DSB runs on the PGM and represents one Siemens device in the PROFIBUS network.
The Siemens ET200M DSB processes the raw data from the Siemens devices and converts it to the PDC format
supported by the Experion. The Siemens ET200M DSB communicates with the master PGM for data
conversion.
A single Siemens ET200M DSB can support up to 16 input/output modules.
The Siemens ET200M DSB has 9 card physical slots. The first slot is for the station and the remaining eight
slots are for the I/O modules. Logically, the ET200M I/O rack is divided in to 11 logical slots. The first 3 slots
are reserved and the remaining slot 4 through slot 11 are for the I/O modules. The extended diagnostics for the
ET200M has diagnostic data for the modules in I/O rack slots. It also contains the channel-specific diagnostics
for channels of modules in the I/O rack slots.
The following table summarizes the I/O modules supported by the Siemens ET200M DSB and also the number
of channels supported by these I/O modules.
I/O module
Number of channels supported
Siemens analog input module
8, 4, 2
Siemens analog output modules
8, 4, 2
Siemens digital input module
32, 16, 8, 4
Siemens digital output module
32, 16, 8, 4
Set of mixed digital input and output module
-
Supported gateways
The Siemens ET200M DSB supports following gateways.
• IM 153-1
• IM 153-2
Related topics
“Device Support Block (DSB) overview” on page 112
“CEAG Device Support Block (CEAGDSB)” on page 129
“Generic Drive Device Support Block (DRIVEDSB)” on page 124
“Generic Device Support Blocks (GENPADSB and GENPAGWDSB) for PA devices” on page 122
“Siemens AS-i Link Device Support Block (Siemens DP/AS-i-Link DSB)” on page 134
“Turck Excom Device Support Block (Turck Excom DSB)” on page 142
“Generic Device Support Blocks (GENDSB and GENIODSB)” on page 120
7.9.1 I/O modules supported by the Siemens ET200M DSB
The following tables lists the I/O modules supported by the Siemens ET200M DSB.
Siemens ET200M DSB
Digital Module
Order Number
Digital Input Module SM 321; DI 32_24 VDC
(6ES7 321-1BLx0-0AA0)
Digital Input Module SM 321; DI 32_120 VAC
(6ES7 321-1EL00-0AA0)
Digital Input Module SM 321; DI 16_24 VDC
(6ES7 321-1BHx2-0AA0)
7 DEVICE SUPPORT BLOCK (DSB)
138
www.honeywell.com
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...