7.16 Configuring the PDC
The
PDC
tab of the DSB block is used to define the PDCs. The slave device data is accessed through the
configuration in the PDC tab. The PDC tab is divided into upper and lower grid. The upper grid is used to
configure the module types. The lower grid displays the channels and the channel-related information of the I/O
modules selected in the upper grid.
Attention
•
You can use the following procedure for configuring parameters that are generic to all DSBs. However, you must
refer to the <DSB name> specific PDC configuration guidelines section for information on DSB specific
parameters. For example, for Generic DSB specific PDC configuration, you can refer to the section “Generic DSB
specific PDC configuration guidelines.”
•
For Turck Excom DSB and Siemens ET200M DSB, the PDC configuration must be done through IOM
configuration tab.
Perform the following steps to configure the PDC
1
Click the
PDC
tab in the DSB block configuration form.
The PDC tab configuration form appears.
2
In the
PDC Type
list, select the appropriate I/O module.
This list represents the module types supported by the DSB. The PDC types that appear in this list may vary
based on the DSB that is selected.
When you select a specific PDC type in the upper grid, all the channel information and the channel
parameters of the configured I/O modules appear in the lower grid.
Attention
After the PDC is associated with a PIOMB, you cannot modify the PDC type.
3
In the
PDC Description
column, type a description for the PDC.
The description you provide here can be used to identify the correct PDC when associating the PDCs to the
PIOMB.
4
In the
Net Tag Name
column, select the correct net tag name against the PDC type.
The tag names that appear in this list are the names that you have defined while configuring the slave device
in the “Profibus Network Configuration Tool”. The net tag name is unique for each I/O module. You cannot
select the same net tag name for two I/O modules inside a slave device. However, you can use the same net
tag name for another slave device.
5
Select the
Hold on failure
check box if you want the DSB to hold the last output value in the event of a
communication error between the C300 and the PGM.
6
In the
Number of Channels
column, type the number of channels that the PDC supports.
By default, the number of channels is set to "1."
7
In the
Channel Description
column, type a brief description (maximum of 32 characters) of the channel.
8
In the
Channel Type
column, select the type of the channel.
• The channel types can be Digital Input, Digital Output, Analog Input, and Analog Output.
• The values that appear in this list may vary based on the DSB selected.
• If you have used the fixed PDC types, the channel types are displayed automatically.
• You must define the channel type if you have used the configurable input/output PDCs.
9
In the
Channel Data Type
column, select the data type of the channel.
• The channel data types can be Boolean, Uint8, Uint16, Uint32, Int8, Int16, Int32, and Float32. The
values that appear in this list may vary based on the DSB selected.
• If you have used the fixed PDC types, the channel data types are displayed automatically.
7 DEVICE SUPPORT BLOCK (DSB)
156
www.honeywell.com
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...