7.18 Monitoring DSB block
Tip
In this section, the state and command parameters of the DSB block are listed for quick reference. For detailed
information about these parameters, you need to refer to the PROFIBUS Gateway Module Parameter Reference
guide.
Related topics
“DSB block state after configuration and load” on page 171
“DSB block status parameters” on page 174
“Monitoring the DPV1 data records” on page 174
“DSB block icons” on page 174
“DSB block diagnostic alarms” on page 175
7.18.1 DSB block state after configuration and load
Main tab
The Slave State (SLAVESTATE) parameter will be "COMMUNICATING." In the event of a communication
loss between the master and the slave device, the Connection Lost Counter (DSBCONNLOSTCOUNT) will
display the count.
Slave Status tab
The Slave Device (SLAVEDEVICE) and the Watchdog On (WATCHDOGON) LEDs will be green in normal
conditions. If a slave device has extended diagnostics, the Extended Diagnostics (EXTENDEDDIA) LED
appears red. Similarly, the corresponding LEDs will appear red based on the error condition.
You can view the extended diagnostics details from the Field Network Configuration tab. See “Viewing the
slave device's extended diagnosis” on page 101.
Alarms tab
Attention
This tab is only applicable to the Generic DSBs and the DRIVEDSB. After the Generic DSBs or the DRIVEDSB is
loaded, if any of the defined alarms is active, the respective Condition Status (USERCONDITSTA) parameter will be
"ON" (checked).
The Condition Status (USERCONDITSTA) parameter will be "On (1)" if any of the user-defined alarm
conditions exists.
PDC tab / IOM Configuration tab
The following values in the
PDC
tab are updated from the DSB running on the PGM.
•
PDCSTATE
- The state (PDCSTATE) of the PDCs that are configured but not connected to a PIOMB will
be "PDC Configured." The state of the PDCs that are connected to the PIOMB will be "PDC Connected."
However, the state of the PDCs that are not configured will be "PDC not Configured."
•
DATAMODULENBR
- The Data Module Number (DATAMODULENBR) parameter will display the data
module number of the PDC provided by the “Profibus Network Configuration Tool”.
•
PDCDATASIZE
- The Data Size (PDCDATASIZE) parameter will display the data size of the data module
provided by the “Profibus Network Configuration Tool” appears in the
Data Size
column. This number
appears in the Monitoring view after the Generic DSBs is loaded.
7 DEVICE SUPPORT BLOCK (DSB)
171
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...