8.5 Monitoring a PBHIOMB block
In this section, the state and command parameters of the PBHIOMB block are listed for quick reference. For
detailed information about these parameters, see
PROFIBUS Gateway Module Parameter Reference
.
8.5.1 PBHIOMB block state after configuration and load
The behavior of the PBHIOMB block after loading the PBHIOMB block is described.
Main tab
The PBHIOMB block can be loaded only if a PDC Name Reference (PDCNAMEREF) is configured.
When the PBHIOMB block is loaded, the
• PDC Name Reference (PDCNAMEREF) displays the associated PDC name.
• associated DSB block name is displayed in the Slave Name.
• Slot Number(SLOTNUM) displays the physical slot number of the PBHIOMB.
• Number Of Channels (NUMCHANS) displays the number of HART channels configured in the PBHIOMB.
• PDC Grouped (PDCGROUPED) displays whether the PDC is grouped.
HART Configuration tab
The HART Configuration tab displays the Directory Process Data Index (DIRPROCDATAINDEX) value. You
can configure the HART channels using the HENABLE parameter. The Channel Name (CHNLNAME)
parameter displays the HART channel name that is configured under the PBHIOMB.
8.5.2 PBHIOMB block status parameters
The following sections explains the status of HART channels.
Auto Discovery Enabled (AUTODISCOVERYENABLED)
The AUTODISCOVERYENABLED parameter indicates whether the auto-discovery can be initiated.
AUTODISCOVERYENABLED parameter is set as "ON" when the PBHIOMB has the PBHCHANNEL that is
not enabled and can be used for future HART configuration. For example, the HART-enabled (HENABLE)
parameter has the five channels for HART configuration. However, you have enabled only three channels and
the other two channels are not enabled.
AUTODISCOVERYENABLED parameter is set as "OFF" when the PBHIOMB has all the PBHCHANNELs
are enabled and available for configuration in the Project view.
Auto Discovery In Progress (AUTODISCOVERYSTATUS)
The AUTODISCOVERYSTATUS parameter indicates whether the auto-discovery of the HART devices is in
progress.
Find HART Devices (FINDDEVICES)
The FINDDEVICES parameter enables you to initiate the auto-discovery of the HART devices.
Note
The Find HART Devices (FINDDEVICES) parameter is enabled only when the Auto Discovery Enabled
(AUTODISCOVERYENABLED) parameter is indicated as GREEN.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
198
www.honeywell.com
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...