8.6 Monitoring the PBHCHANNEL block
In this section, the state and command parameters of the PBHCHANNEL block are listed for quick reference.
For detailed information about these parameters, see
PROFIBUS Gateway Module Parameter Reference
.
Attention
The update rate of parameters, depends on the following conditions:
•
Configured Link Baud Rate
•
Bandwidth percentage for DPV1 requests configured in the PBLINK block
•
Number of HART devices configured per slave
•
Whether the HART IOMs perform internal scan
•
IOMs response rate which depends on number of modems in IOM
•
Priority of request configured in channel
•
Number of DPV1 data record configured per slave in the DSBs
•
Existence of FDM or other DTM clients
•
Wrong channel configuration which results in wait until timeout
•
PB Slave response time for DPV1 request
8.6.1 PBHCHANNEL HART Status-related parameters
General Device Status
The standard diagnostics that are active for the connected HART device can be monitored in the
General
Device Status
.
Device Specific Status (Command 48)
The Command 48 diagnostics that are active for the connected HART device can be monitored in the
Device
Specific Status (Command 48)
.
HART Communication Status (HCOMSTS)
The HART Communication Status (HCOMSTS) parameter displays the communication status with the HART
device.
Last Communication Failure (HCOMFAIL)
The Last Communication Failure (HCOMFAIL) parameter indicates the last communication failure based on
the status of the HCOMSTS parameter.
Failed Command (HCMDFAIL)
The Failed Command (HCMDFAIL) parameter indicates the HART command number that failed.
Failed Response Code (HCMDRESP)
The Failed Response Code (HCMDRESP) parameter indicates the response code from the failed command
listed in the HCMDFAIL parameter.
Communication Errors (HNCOMERR)
The Communication Errors (HNCOMERR) parameter indicates the number of communication errors occurred
from last reset.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
201
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...