22
Connecting the RPS-1000 to the FACP
Hardware Installation
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
Figure 3.2 Battery Connection
3.3 Connecting the RPS-1000 to the FACP
1.
Connect the RPS-1000 to the appropriate SBUS. The RPS-1000 can be connected directly to the FACP or can be daisy-chained to
another RPS-1000. Figure 3.3 and Figure 3.4 show both connections.
2.
Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2.1 shows the location of the DIP switches on the RPS-1000
board.
3.
Configure the RPS-1000 module by adding it to the system (through JumpStart or manually). You can also assign a name to the
module. These procedures are described in the FACP Installation Manuals. See table below.
Red
To Panel
Black
12V Battery
12V Battery
Battery Jumper
(P/N 140694)
Replace batteries every 5 years.
ECS Series Model Number
FACP Installation Manual
IFP-2000ECS
151430-L8
IFP-1000ECS
151460
IFP-100ECS
151458
IFP-300ECS
LS10145-001SK-E
IFP-2100ECS
LS10143-001SK-E