29
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Hardware Installation
Flexputs™ I/O Circuits
3.5.5 Installing 4-Wire Smoke Detectors
Any compatible UL listed four-wire smoke detector can be used with the RPS-1000 panel (see Appendix A for list of compatible smoke
detectors). Figure 3.12 and Figure 3.13 illustrate how to connect a UL listed four-wire detector to the control panel.
Installing a Class B 4-Wire Smoke Detector
Figure 3.14 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1.
Up to three Class B 4-wire smoke detector loops can be connected to the control panel at once.
2.
Each Class B loop input is paired with a unique power source as shown in Figure 3.14.
3.
Each loop gets smoke power from the even numbered I/O circuit and the contact input is connected to the odd numbered I/O circuit.
Figure 3.14 Class B 4-Wire Smoke Detector Connections
Installing 4-Wire Class A Smoke Detectors
Figure 3.15 illustrates how to install 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1.
Up to two Class A 4-wire loops can be connected to the control panel at once.
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.13 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
Air Products
PAM-2
Model 160150
Supervision
Module
4.7 k
EOL Resistor
ESL 449CT
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
“Class B 4-Wire Smoke Detector Connections” on page 29 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
Summary of Contents for Farenhyt RPS-1000
Page 49: ......