RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Before You Begin Installing
Inventory
Section 2: Before You Begin Installing
2.1 Inventory
The Model RPS-1000 ships with the following hardware:
•
A cabinet with all hardware assembled
•
Two keys for the front door
•
Ten 4.7K ohm end-of-line resistors
•
A battery cable for batteries wired in series
2.2 Environmental Specifications
It is important to protect the RPS-1000 control panel from water. To prevent water damage, the following conditions should be
AVOIDED when installing the units:
•
Do not mount directly on exterior walls, especially masonry walls (condensation)
•
Do not mount directly on exterior walls below grade (condensation)
•
Protect from plumbing leaks
•
Protect from splash caused by sprinkler system inspection ports
•
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the RPS-1000, the unit should be mounted where it will NOT be exposed to temperatures outside the
range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
2.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly
recommend that you download the most current version of software for each product prior to commissioning any system. Contact Tech-
nical Support with any questions about software and the appropriate version for a specific application. Software updates can be found at
NOTE:
For UL installations, 4.7k
end-of-line resistor (ordered separately) must be used.