[4] DETECTOR INSTALLATION 

[4.1] VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY 

Model D365PL detectors are designed to be used in air handling systems hav-
ing air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 
12 feet can be accommodated. Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

[4.2] DETERMINE MOUNTING LOCATION AND CONFIGURATION

On ducts wider than 18 inches it is recommended that the detector be 
mounted downstream of a bend, obstruction in the duct, or the supply or 
return air inlet. 

Exception: Installation of duct detectors can be on or within a commercial 
packaged rooftop heating and air-conditioning system, fire/smoke dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.

Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in Figure 2. If mounting in the square configuration, 
remove the rear attachment screw, rotate the unit at hinge, and replace the 
screw into the new attachment hole as shown in Figure 2. Do NOT remove 
the hinge screw during this process. Final installation approval shall be based 
upon passing differential pressure and smoke entry tests described in Section 
6 Measurement Tests.

FIGURE 2.

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[4.3] DRILL THE MOUNTING HOLES

Remove the paper backing from the mounting template supplied. Affix the 
template to the duct at the desired mounting location. Make sure the template 
lies flat and smooth on the duct. 

[4.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION

Center punch at four target centers: two “A” for sampling tubes and two “B” 
for the rectangular configuration mounting tabs as shown on mounting tem-
plate. Drill pilot holes at target “A” centers and cut two 1.375 inch diameter 
holes using a 1

3

8

-inch hole saw or punch. Drill .156 inch diameter holes using 

5

32

 inch drill at target “B” centers.

[4.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION

Center punch at four target centers: two “A” for sampling tubes and two “C” 
for the square configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes 
using a 1

3

8

-inch hole saw or punch. Drill .156 inch diameter holes using a 

5

32

 

inch drill at target “C” centers. If desired, drill an additional .156 inch hole at 
the location of one of the mounting tabs on the lower housing.

[4.4] SECURE THE DUCT DETECTOR TO THE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION: Do not overtighten the screws.

[5] SAMPLING TUBE INSTALLATION

[5.1] SAMPLING TUBE SELECTION

The sampling tube must be purchased separately. Order the correct length, 
as specified in Table 1, for width of the duct where it will be installed. The 
sampling tube length must extend across at least 

5

/

8

 of the width of the duct 

for optimal performance.

The sampling tube is always installed with the air inlet holes facing into the 
air flow. To assist proper installation, the tube’s connector is marked with an 
arrow. Make sure the sampling tube is mounted so that the arrow points into 
the airflow as shown in Figure 3. Mounting the detector housing in a vertical 
orientation is acceptable provided that the air flows directly into the sam-
pling tube holes as indicated in Figure 3. The sampling tube and exhaust tube 
can be mounted in either housing connection as long as the exhaust tube is 
mounted downstream from the sampling tube.

TABLE 1. SAMPLING TUBES RECOMMENDED FOR DIFFERENT DUCT 

WIDTHS

Outside Duct Width

Sampling Tube Recommended*

Up to 1 ft.

DST1

1 to 2 ft.

DST1.5

2 to 4 ft.

DST3

4 to 8 ft.

DST5

8 to 12 ft.

DST10 (2-piece)

*Must extend a minimum of 

5

/

8

 the duct width

FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS

 

WIRING 

COMPARTMENT

SAMPLING 

TUBE

SOLD 

SEPARATELY

EXHAUST TUBE

SENSOR MODULE

SENSOR HEAD

WIRING 

COMPARTMENT 

COVER

SENSOR 

MODULE 

COVER

 H0569-20

  

I56-6626-000 

 

 2/26/2019

Summary of Contents for Fire-Lite Alarms D365PL

Page 1: ...rent 200 µA 24 VDC one communication every 5 seconds with LED blink enabled Max Alarm Current LED on 6 2 mA 24 VDC NOTE The D365PL comes with the sensor head factory installed part number SD365R IV TABLE OF CONTENTS PAGE 1 Limitations of Duct Smoke Detectors 1 2 General Description 1 3 Contents of the Duct Smoke Detector Kit 1 4 Detector Installation 2 5 Sampling Tube Installation 2 6 Measurement ...

Page 2: ... A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 3 2 FOR SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at four target centers two A for sampling tubes and two C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and...

Page 3: ...er than necessary to span the duct width Use a 0 193 inch diameter 10 drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube CAUTION This procedure should only be used as a temporary fix It is not intended as a permanent substitute for ordering the c...

Page 4: ...ENANCE PROCEDURES Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms ...

Page 5: ...ING DIAGRAM FOR D365PL TO RA100Z RA100Z RA RA REMOTE ALARM LED OPTION 1 PER UNIT H0570 05 Note Remove jumper when using RA100Z with the intelligent duct smoke detector The RTS151 RTS151KEY Remote Test Station facilitates test of the alarm ca pability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The D365PL duct smoke detector must ...

Page 6: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the d...