background image

[7] FIELD WIRING; INSTALLATION GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction. Proper wire gauges should be used. 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring (the wiring between detectors or from detector to auxiliary 
devices), it is usually recommended that single conductor wire be no smaller 
than 18 gauge. The duct smoke detector terminals accommodate wire sizes up 
to 12 gauge. Flexible conduit is recommended for the last foot of conduit; solid 
conduit connections may be used if desired.

Duct smoke detectors and alarm system control panels have specifications for 
Signaling Line Circuit (SLC) wiring. Consult the control panel manufacturer’s 
specifications for wiring requirements before wiring the detector loop. 

[7.1] WIRING INSTRUCTIONS

Disconnect power from the communication line before installing the D365PL 
duct smoke detector. 

The D365PL detectors are designed for easy wiring. The housing provides a 
terminal strip with clamping plates. Wiring connections are made by sliding 
the bare end under the plate, and tightening the clamping plate screw. See 
Figure 6 below for system wiring.

FIGURE 6. SYSTEM WIRING DIAGRAM FOR D365PL 

COMM. 

LINE (+)

UL/FM LISTED 

CONTROL 

PANEL

1ST 

DETECTOR

IN LOOP

2ND 

DETECTOR

IN LOOP

COMM. 

LINE (–)

COMM. 

LINE

HO572-00

[7.2] SET THE ADDRESS 

Set the desired address on the sensor head code wheel switches on the back 
of the sensor head.

FIGURE 7. ROTARY ADDRESS SWITCHES

 

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

 C0162-00

[8] VERIFICATION OF OPERATION 

[8.1] INSTALL THE COVER

Install the covers making sure that the cover fits into the base groove. Tighten 
the seven screws that are captured in the covers. Note that the cover must be 
properly installed for proper operation of the sensor.

[8.2] POWER THE UNIT

Activate the communication line on terminals COM + and COM –.

[8.3] DETECTOR CHECK

Standby – If programmed by the system control panel, look for the presence of 
the flashing LEDs through the transparent housing cover. The LED will flash 
with each communication.

Trouble – If programmed by the system control panel and the detector LEDs 
do not flash, then the detector lacks power (check wiring, missing or improp-
erly placed cover, panel programming, or power supply), the sensor head is 
missing (replace), or the unit is defective (return for repair).

[8.4] DUCT SMOKE DETECTOR TEST & MAINTENANCE PROCEDURES

Test and maintain duct smoke detectors as recommended in NFPA 72. The 
tests contained in this manual were devised to assist maintenance personnel 
in verification of proper detector operation. 

Before conducting these tests, notify the proper authorities that the smoke 
detection system will be temporarily out of service. Disable the zone or system 
under test to prevent unwanted alarms.

[8.4.1] TEST THE UNIT

1.   M02-04-00 Magnet Test (not included) – This sensor can be function-

ally tested with a test magnet. The test magnet electronically simulates 
smoke in the sensing chamber, testing the sensor electronics and connec-
tions to the control panel. 

2.   Remote Test Accessory – The use of a remote accessory for visible indica-

tion of power and alarm is recommended. 

 

 Verify system control panel alarm status and control panel execution of 
all intended auxiliary functions (i.e. fan shutdown, damper control, etc.).

 

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status. Coded signals, transmitted from the panel, can cause the LEDs 
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED operation and expected delay to alarm.

[8.4.2] THE DETECTOR MUST BE RESET BY THE SYSTEM CONTROL 

PANEL

[8.4.3] SMOKE ENTRY TEST USING AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described in Section 6 Measurement 
Tests.

Drill a ¼-inch hole 3 feet upstream from the duct smoke detector. With the air 
handler on, measure the air velocity with an anemometer. Air speed must be 
at least 100 FPM. Spray aerosol smoke* into the duct through the ¼-inch hole 
for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 
duct smoke detector alarms, air is flowing through the detector. Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 
chamber and reset the duct smoke detector at the panel. Use duct tape to seal 
the aerosol smoke entry hole. Remember to replace the cover after the test or 
the detector will not function properly.

Additionally, canned aerosol simulated smoke (canned smoke agent) may be 
used for smoke entry testing of the smoke detector. Tested and ap proved aero-
sol smoke products are: 

Manufacturer 

Model

HSI Fire & Safety  25S, 30S (PURCHECK) 
SDi 

SMOKE CENTURIAN, SOLOA4, SMOKESABRE, TRUTEST 

No Climb

TESTIFIRE 2000

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary 
by manufacturer. Misuse or overuse to these products may have long term 
adverse effects on the smoke detector. Consult the canned smoke agent manu-
facturer’s published instructions for any further warnings or caution state-
ments.

  

I56-6626-000 

 

 2/26/2019

Summary of Contents for Fire-Lite Alarms D365PL

Page 1: ...rent 200 µA 24 VDC one communication every 5 seconds with LED blink enabled Max Alarm Current LED on 6 2 mA 24 VDC NOTE The D365PL comes with the sensor head factory installed part number SD365R IV TABLE OF CONTENTS PAGE 1 Limitations of Duct Smoke Detectors 1 2 General Description 1 3 Contents of the Duct Smoke Detector Kit 1 4 Detector Installation 2 5 Sampling Tube Installation 2 6 Measurement ...

Page 2: ... A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 3 2 FOR SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at four target centers two A for sampling tubes and two C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and...

Page 3: ...er than necessary to span the duct width Use a 0 193 inch diameter 10 drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube CAUTION This procedure should only be used as a temporary fix It is not intended as a permanent substitute for ordering the c...

Page 4: ...ENANCE PROCEDURES Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms ...

Page 5: ...ING DIAGRAM FOR D365PL TO RA100Z RA100Z RA RA REMOTE ALARM LED OPTION 1 PER UNIT H0570 05 Note Remove jumper when using RA100Z with the intelligent duct smoke detector The RTS151 RTS151KEY Remote Test Station facilitates test of the alarm ca pability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The D365PL duct smoke detector must ...

Page 6: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the d...

Reviews: