156
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Appendix J: Canadian Applications
•
The ES-200XC is supplied standard with the DP-ES-R Dress Panel for Canadian applications.
•
When installing and programming the FACP, the Canadian Option must be set to
ON
prior to any other panel programming (refer to
“Canadian Option” on page 79 of the Programming Section of this manual).
•
At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary operator interface. Wiring to the ANN-
LED must be in metal conduit and must be connected to the FACP’s Primary ANN-BUS.
•
If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit.
•
The installer must write in the
Date of Final Assembly
on the Master Marking and Warranty Label located on the FACP backbox
door.
•
Positive Alarm Sequence (PAS), the Pre-Signal option, and the Auto-Silence option are not available for Canadian applications.
•
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
•
The F2 function key is automatically configured to perform a two-stage bypass when pressed which advances NAC coding directly
to the second stage alarm.
•
The F3 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation. This
prevents the NAC from advancing to the second-stage alarm.
•
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
•
AlarmNet supervision settings for panels communicating by Cellular-only or Ethernet-only method are fixed at 3 minutes and
cannot be changed regardless of programming selection.
Figure J.1 FACP Minimum Configuration - Single ANN-LED
FACP
ANN-LED
ANN-LED
ANN-I/O
ANN-S/PG
ANN-RLY
Optional Secondary ANN-BUS (data on
connector TB10, power on TB11
Terminals 5&6 with power programmed
as non-resettable)
Primary ANN-BUS (data
on connector TB9, non-
resettable power on
TB11 Terminals 1&2) in
metal conduit (adjacent
to FACP)
e
s
2
0
0
c
-a
n
n
le
d
.w
m
f
optional
ECC-50/100
audio system
ANN-100
FIRE SYSTEM
ACTIVE
SYSTEM
CONTROL
ALL
CALL
1
2
3
4
5
6
7
8
9
10
11
12
13
18
19
20
21
22
23
24
16
17
14
15
LIT
FI
®
AL
by Honeywell