50
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
User Programming
3.2 User Programming
The ES-200X is completely field programmable and requires no special software skills.
While programming the ES-200X, the fire pro-
tection capabilities of the control panel are enabled.
Site-specific programming may be accomplished in any of the following ways:
•
Autoprogramming Feature
- This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without
the necessity of programming each device individually. Refer to “Autoprogram” on page 52 for a detailed description of
Autoprogramming.
•
Manual programming or editing, using the FACP keypad or a PC keyboard
•
Remote Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based
computer and Ethernet connection. For programs requiring a large amount of data entry, this method may be preferred. The FS-
Tools programming utility can be downloaded from www.firelite.com for this purpose.
•
Local Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based
computer and the FACP USB connection. For programs requiring a large amount of data entry, this method may be preferred. The
FS-Tools programming utility can be downloaded from www.firelite.com for this purpose.
•
The
System Normal
screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated
below:
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or supervisory event exists at the panel, the
event must be cleared before entering Programming mode. To access any of the programming or read status features, the
Enter
or
Mode
key must be pressed, which will cause the LCD to display the following:
Last Event
End
Clear
Delete
ESC
Esc
RECALL
Insert
*
*
#
#
@
@
A - Z
A - Z
0 - 9
0 - 9
■
(on
YZ
key)
Space bar
—
—
/
/
•
•
ENTER
Enter
F1
F1
F2
F2
F3
F3
F4
F4
ACK/STEP
F5
SILENCE
F6
DRILL
F7
RESET
F8
SYSTEM NORMAL
10:00A 010118
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FSTOOL UP/DOWNLOAD
4=USB UP/DOWNLOAD