ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
91
Master Programming Level
Programming
Pressing
1
for
Type
will display the following screens:
Press the number corresponding to the module/device type that is installed with the selected address.
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
Since the options for each of these module types can be individually set, pressing
2
for
Module Options
, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ANN-I/O Options
Pressing
2
for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the follow-
ing screen:
The first screen indicates that the ANN-I/O at ANN-BUS address 1 is programmed to annunciate SLC Loop #1 addressable Detectors
with addresses 1 through 30. The programming can be changed using ANN-I/O Address Screens 2 and 3.
Pressing
1
while viewing ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information.
Pressing
1
while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in “
Pressing
2
while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated.
Module Type Screen #1
Module Type Screen #2
Module Type Screen #3
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-100 MODULE
ANN-BUS MODULE TYPE
1=ANN-I/O MODULE
2=ANN-S/PG MODULE
3=ANN-LED MODULE
ANN-BUS MODULE TYPE
1=ANN-RLY MODULE
2=ANN-ACC
2=ANN-ECC
NOTE:
If the module type selected is the
ANN-80, ANN-100, ANN-S/PG,
or
ANN-ACC
or if
Not Installed
is selected, the ANN-BUS
Address Screen shown on the previous page will be displayed following the module selection. The options selected for each of these
modules will be the same for all modules of the same type (refer to “ANN-S/PG (Print) Options” on page 98 and “
ANN-80/100 Options
” on
page 98).
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen
ANN-I/O - ADDR X-1
SLC 1 DET 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
ANN-I/O - ADDR X-1
1=POINT/ZONE POINT
ANN-I/O Address Screen #2
ANN-I/O - ADDR X-1
1=RANGE PT001-030
2=DET/MOD DET
ANN-I/O Address Screen #3