3.7.5 System
Pressing
2
while viewing Maintenance Screen #2, will display the following screen:
Pressing
1
while viewing System Screen #1 will display the following:
Pressing
1
while viewing NAC Screen #1 will cause the display to change to
NAC1 Yes
. This will allow the selected main circuit board
NAC to activate its devices. Each press of the
1
key will cause the display to toggle between
NAC1 Yes
and
NAC1 No
. The same action
is performed for the other 3 NAC circuits by selecting the number of the desired output circuit.
To enable remote synchronization, press the
3
key while viewing System Screen #2. Each press of the key will toggle the screen between
Rem Sync Enab Yes
and
Rem Sync Enab No
.
Pressing
1
while viewing System Screen #2 will cause the following screen to be displayed:
To change the time, press
1
to display the following screen:
A flashing cursor will appear on the left side of the display. Enter the four digit number corresponding to the time (0000 - 1259). When
the fourth digit is entered, the cursor will move one position to the right. Press
1
for AM or
2
for PM to complete entering the time. The
display will return to the Time and Date Screen displaying the new time.
To change the date, press
2
while viewing the Time and Date Screen. The following screen will be displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and two digit year. The cursor will
move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and
Date Screen which will show the new date.
To enable the onboard battery charger, press the
2
key while viewing System Screen #2. Each press of the
key will toggle the screen between
Charger Enab Yes
and
Charger Enab No
. The setting must say
Charger
Enb No
when an external battery charger is being used.
If a 4XTMF Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing
3
while viewing System Screen #2 will cause the display to toggle to
4XTM Spv Enab. Yes
, which
means there is a 4XTMF installed. Each press of the
1
key will cause the display to toggle between
4XTM Spv Enab. No
and
4XTM Spv
Enab. Yes
.
3.7.6 Zone Setup
Pressing
3
while viewing Maintenance Screen #2 will display the following screen:
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
SYSTEM
1=NACS ENAB 1,2,3,4
2=REM SYNC ENAB YES
System Screen #1
SYSTEM
1=TIME/DATE
2=CHARGER ENAB YES
3=4XTM SPV ENB YES
System Screen #2
SYSTEM
1=NACS ENB 1,2,3,4
2=REM SYNC ENAB YES
System Screen #1
ENABLE NACS
1=NAC1 N 3=NAC3 N
2=NAC2 N 4=NAC4 N
Disable NACs Screen
SYSTEM
1=TIME/DATE
2=CHARGER ENAB YES
3=4XTM SPV ENAB NO
System Screen #2
TIME AND DATE
1=TIME 01:00 AM
2=DATE 05-04-2017
3=CLOCK FORMAT 12HR
Time and Date Screen
ENTER TIME
01:00 AM
1=AM 2=PM
Time Screen
ENTER DATE
MONTH DAY YEAR
05-04-17
Date Screen
SYSTEM
1=TIME/DATE
2=CHARGER ENAB YES
3=4XTM SPV ENAB NO
System Screen #2
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
ZONE SETUP
1=ENABLE
2=DISABLE
3=SPECIAL PURPOSE
Zone Setup Screen