ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Product Description
Specifications
•
Optional FS-Tools programming utility for local or remote Upload/Download of programming and data (available for download
from www.firelite.com)
•
Compatible with Fire-Lite’s devices in LiteSpeed and CLIP mode (refer to SLC Wiring Manual for a list of compatible addressable
devices)
•
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible
addressable devices)
•
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
•
ANN-BUS for connection to following optional modules:
ANN-80 Remote Annunciator (UL applications only)
ANN-100 (FM and Canadian applications only)
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Form-C Relay Module
ANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for Canada and emergency signaling)
ANN-RLED Annunciator Module annunciates alarms only
•
Automated activation of the legacy ACC-25/50(ZS/T) Audio-Command-Center
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB13
Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 amps, auto-sensing. No switch or jumper required.
Wire size: minimum 14 AWG (2.00 mm
2
) with 600 V insulation
Battery (Sealed Lead Acid Only) - J15
Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.5 amps
Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. The BB-26 Battery
Box holds two 26 Amp Hour batteries and the CHG-75. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75
or CHG-120F Battery Charger and BB-55F Battery Box).
Minimum Battery Size: 7 Amp Hour
Note: Refer to the programming section to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB12
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 143)
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit
Refer to
SLC Wiring manual
for wiring information
Notification Appliance Circuits - TB4, TB5, TB6, & TB7
Four (4) Class B NAC circuits or four (4) Class A circuits
Special Application, filtered power
Power-limited circuitry
NAC wiring requirements refer to “NAC Wiring” on page 144
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps special application, 250 mA regulated (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 k
Ω
, ½ watt (P/N 71252 UL listed) required for each circuit; system capable of 1.9 k
Ω
- 22 k
Ω
ELR range.
Refer to the
Device Compatibility Document
for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB1, TB2, & TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.6 on page 26 for information on power-limited relay circuit wiring
Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB11, Terminals 1 (+), 2 (-), 3(+), & 4(-)
(programmable)
Factory-set as nonresettable, suitable for powering annunciators
Programmable Class A or Class B wiring
Maximum ripple voltage: 20mV
RMS
Total DC current available is up to 1.0 amp (see Figure 1.1 on page 15)
Power-limited circuit
Note: Refer to the programming section to configure power as resettable/non-resettable and for Class A or Class B wiring.