ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Product Description
Accessories
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a
disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to
open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the
right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow
supervision of the module.
1.6 Accessories
1.6.1 FS-Tools Programming Utility
The FS-Tools Programming Utility can be used to locally or remotely program the FACP from most Windows® compatible computers
(PC), running Windows 7 or newer, 32 or 64 bit. The FACP program files can also be created and stored on the PC for future download
to the control panel. FS-Tools can be downloaded from www.firelite.com. A standard USB cable with male-A to male-A connectors,
which must be purchased separately, is required for local connection of the PC to the USB port J20 on the FACP main circuit board.
Remote programming requires that the PC have a GSM or Ethernet connection.
FS-Tools also provides the ability to create panel program files on a USB flash drive. The drive can then be plugged into USB port J20
on the FACP main circuit board.
Important:
Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “FS-Tools
Upload/Download” on page 123). Remote interrogation of panel programming, history logs, detector status, etc., is possible without
enabling the remote download option.
1.6.2 Dress Panel
An optional dress panel DP-ES-Ris available for the ES-200X (required by ULC for Canadian installations). The dress panel restricts
access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of
the dress panel and the ground stud in the backbox.The dress panel mounts to the backbox with two (2) #6-32 screws. The ES-200XC is
supplied standard with a dress panel.
1.6.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring adds 1.5” of wall coverage around the backbox,
concealing hardware and providing a finished appearance for a semi-flush mounted panel.
1.6.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is
mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
1.6.5 Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be dis-
abled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box.
Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the
CHG-75 Manual
for additional information.