76
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
A flashing cursor will appear in the lower left corner of the display. Type the three digit control module delay in seconds (000 to 180 sec-
ond delay). When the third digit is entered, the display will return to the Delay Screen which will indicate the new delay time. Refer to
the table on page 49 for permissible settings.
NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure by pressing
2
while
viewing System Setup Screen #2. The following screens will be displayed:
The Notification Appliance Circuits can be configured independently by pressing
1
for NAC 1,
2
for NAC 2,
3
for NAC 3, or
4
for NAC
4.
The following screens will be displayed for each selection:
Enabled
Pressing
1
while viewing NAC Screen #1 will cause the display to change to
Enabled No
. This will prevent the selected main circuit
board NAC from activating its devices. Each press of the
1
key will cause the display to toggle between
Enabled Yes
and
Enabled No
.
Type
The main circuit board NAC type can be programmed by pressing
2
while viewing NAC Screen #1. The
following screen will be displayed. Press the down arrow key to view additional screens:
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the
display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
Silenceable
Pressing
3
while viewing NAC Screen #1 will cause the display to change to
Silenceable No
. This will prevent the selected main circuit
board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the
3
key will cause the
display to toggle between
Silenceable Yes
and
Silenceable No
.
Important
: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the
Synced Strobe
feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is
enabled. The visual devices (strobes, etc.) will continue to operate. If the
Strobe Sil Sync
feature is selected, Silence or Autosilence will
turn off both audible and visual devices.
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
NACS
1=NAC 1 3=NAC 3
2=NAC 2 4=NAC 4
NAC Selection Screen
NAC #
1=ENABLED YES
2=TYPE SYNCED STROBE
3=SILENCEABLE YES
NAC Screen #1
NAC #
1=ZONE ASSIGNMENT
000 000 000 000 000
2=SILENC INHIBIT NO
NAC Screen #2
NAC #
1=AUTO SILENCE 00
2=CODING TEMPORAL
NAC Screen #3
NAC #
1=SYNC TYPE S
2=MNS OVERRIDE NO
3=MNS ACTIVE NO
NAC Screen #4
NOTE:
The programming for NAC 1 will determine the operation of the remote power supply sync.
NAC Type Code
Special Function
Bell
None
Horn
None
Strobe
None
Synced Strobe
Synchronized to manufacturer
Strobe Sil Sync
Same as Synced Strobe but Silence turns off audible & visual devices
Future Use
None
Future Use
None
Future Use
None
Blank
None
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1