78
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
Zone
A maximum of five zones can be programmed to each main circuit board NAC. Pressing
1
while viewing
NAC Screen #3 displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is
Z000 for general alarm zone. A flashing cursor will appear on the first
0
to the left. Enter the three digit number corresponding to the
zone that is to be assigned to this NAC. The cursor moves to the next Z*** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zone Z000. When all desired changes have been made, press the
Enter key to store the zone assignments. The display will return to the NAC Screen #3 which will show the zone assignments just
entered.
Silence Inhibit
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for
a period of five minutes. Resetting the FACP will also be prevented for one minute while the NAC pro-
grammed for silence inhibit is activated. Pressing
2
while viewing NAC Screen #3 will cause the display to
change from the factory default of
Silence Inhibit No
to
Silence Inhibit Yes
. Each press of the
2
key will
cause the display to toggle between the two options.
Sync Type
If synchronized strobes were selected as the Type of device installed, the type of synchronization must be
selected in this option. Pressing
1
while viewing NAC Screen #4 will cause the following screen to be dis-
played:
Pressing
1
while viewing this screen will select System Sensor synchronization,
2
will select Wheelock, and
3
will select Gentex.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation sup-
plied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded. To
ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit.
MNS Override
The MNS Override feature, when enabled, allows the ECC-50/100 to override the FACP and turn off an
active NAC or prevent the NAC from activating during a mass notification event. This feature is the oppo-
site of MNS Active. Both cannot be enabled in the system at the same time. Pressing
2
while viewing NAC
Screen #4 will cause the display to change from the factory default of
MNS Override No
to
MNS Override
Yes
. Each press of the
2
key will cause the display to toggle between the two options.
MNS Active
The MNS Active feature, when enabled, allows the selected NAC to activate when an MNS Event occurs
and the FACP receives a message from the ECC-50/100. The selected NAC will activate regardless of zone
mapping. This feature is the opposite of MNS Override. Both cannot be enabled in the system at the same
time. Pressing
3
while viewing NAC Screen #4 will cause the display to change from the factory default of
MNS Active No
to
MNS Active Yes
. Each press of the
3
key will cause the display to toggle between the two
options.
Relays
Pressing
3
while viewing System Setup Screen #2 will allow the programmer to configure two main circuit
board Form-C relays from the following screen:
NAC #
1=ZONE ASSIGNMENT
000
2=SILENC INHIBIT NO
NAC Screen #3
ZONE ASSIGNMENT
Z000
Zone Screen
NAC #
1=ZONE ASSIGNMENT
000
2=SILENC INHIBIT NO
NAC Screen #3
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
3=MNS ACTIVE
NAC Screen #4
NAC SYNC TYPE
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
3=MNS ACTIVE
NAC Screen #4
NAC #
1=SYNC TYPE
2=MNS OVERRIDE
3=MNS ACTIVE
NAC Screen #4
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen