84
ES-200X Series Manual —
P/N LS10131-000FL-E:C 7/25/2018
Programming
Master Programming Level
Select the number of minutes allowed, 1-60, before a fault is shown on the panel.
Primary and Secondary Communication Paths
The Primary and Secondary Communication Path screens are used to configure the methods (primary and
backup) for reporting to central station. Pressing
1
for
Pri
or
2
for
Sec
will display the following screens.
Note that the following information must be entered for both the Primary and Secondary Communication
Paths.
POTS
To configure the communication method to contact central station as a telephone line, select
1
for
POTS
.
The following screens will display.
Enable
To enable the phone line, press
1
while viewing the POTS Line (X) Screen #1 to change the display to
Enabled Yes
. Each press of the
1
key will cause the display to toggle between
Enabled Yes
and
Enabled No.
Account Code
Pressing
3
while viewing POTS (XXX) Path Screen #1 will cause the following screen to be displayed:
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen
will have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys.
Phone Number
Pressing
2
while viewing POTS XXX Path Screen #2 will cause the following screen to be displayed:
The Phone Number screen is used to enter the Central Station phone number that the Communicator will be contacting. A maximum of
20 characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = 2 seconds pause.
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor
to the right one position. Enter the second digit and repeat the process until all digits are entered. Press the
Enter
key to store the phone
number in memory.
COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL CALL LIMIT 0
Communicator Screen #1
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen
POTS XXX COMM PATH
1=ENABLED NO
2=ACCT CODE 000000
POTS (XXX) Path Screen #1
POTS XXX COMM PATH
1=COMM FORMAT
ADEMCO CONTACT ID
POTS (XXX) Path Screen #3
POTS XXX COMM PATH
1=PHONE NUMBER
2035554321
POTS (XXX) Path Screen #2
POTS (XXX) Path Screen #4
POTS XXX COMM PATH
1=TEST TIME INT 24
2=24HR TEST TIME 0100
NOTE:
For UL applications: when POTS is used as the primary communication path, the use of POTS as the secondary transmission path
is only allowed with approval of the local AHJ.
For ULC applications: when POTS is used as the primary transmission path, alarm signals will be sent out on both the primary and
secondary transmission paths.
POTS XXX COMM PATH
1=ENABLED NO
2=ACCT CODE 000000
POTS Comm Path Screen #1
ACCOUNT CODE
ENTER 6 DIGITS
Account Codes Screen
POTS XXX COMM PATH
1=PHONE NUMBER
2035554321
POTS Comm Path Screen #2
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Numbers Screen