background image

[7.1]wIRINg INSTRUCTIONS

Disconnect power from the communication line before installing the D355PL 
duct smoke detector. 

The D355PL detectors are designed for easy wiring. The housing provides a 
terminal strip with clamping plates. Wiring connections are made by sliding 
the bare end under the plate, and tightening the clamping plate screw. See 

Figure 6

 below for system wiring.

[7.2] SET ThE ADDRESS

Set the desired address on the sensor head code wheel switches. on the back 
of the sensor head.

fIgURE 7. ROTARy ADDRESS SwITChES

[8] VERIfICATION Of OPERATION
[8.1]INSTALL ThE COVER

Install the covers making sure that the cover fits into the base groove. Tighten 
the seven screws that are captured in the covers. Note that the cover must be 
properly installed for proper operation of the sensor.

[8.2] POwER ThE UNIT

Activate the communication line on terminals COM + and COM –.

[8.3] DETECTOR ChECk

Standby – If programmed by the system control panel, look for the presence of 
the flashing LEDs through the transparent housing cover. The LED will flash 
with each communication.

Trouble – If programmed by the system control panel and the detector LEDs 
do not flash, then the detector lacks power (check wiring, missing or improp-
erly placed cover, panel programming, or power supply), the sensor head is 
missing (replace), or the unit is defective (return for repair).

[8.4]DUCT SMOkE DETECTOR TEST & MAINTENANCE PROCEDURES

Test and maintain duct smoke detectors as recommended in NFPA 72. The 
tests contained in this manual were devised to assist maintenance personnel 
in verification of proper detector operation. 

Before conducting these tests, notify the proper authorities that the smoke 
detection system will be temporarily out of service. Disable the zone or system 
under test to prevent unwanted alarms.

[8.4.1]TEST ThE UNIT

1.  M02-04-00 Magnet Test (not included) This sensor can be functionally tested 

with a test magnet. The test magnet electronically simulates smoke in the 
sensing chamber, testing the sensor electronics and connections to the con-
trol panel.

2.  Remote Test Accessory – The use of a remote accessory for visible indica-

tion of power and alarm is recommended. 

   Verify system control panel alarm status and control panel execution of all 

intended auxiliary functions (i.e. fan shutdown, damper control, etc.).

   Two LEDs on the sensor are controlled by the panel to indicate sensor sta-

tus. Coded signals, transmitted from the panel, can cause the LEDs to blink, 
latch on, or latch off. Refer to the control panel technical documentation for 
sensor LED operation and expected delay to alarm.

[8.4.2] ThE DETECTOR MUST BE RESET By ThE SySTEM CONTROL PANEL
[8.4.3]SMOkE ENTRy TEST USINg AEROSOL SMOkE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described under Measurement Tests 
on Page 3.

Drill a 

1

4

-inch hole 3 feet upstream from the duct smoke detector. With the air 

handler on, measure the air velocity with an anemometer. Air speed must be 
at least 100 FPM. Spray aerosol smoke* into the duct through the 

1

4

-inch hole 

for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 
duct smoke detector alarms, air is flowing through the detector. Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 
chamber and reset the duct smoke detector at the panel. Use duct tape to seal 
the aerosol smoke entry hole. Remember to replace the cover after the test or 
the detector will not function properly.

*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector 
Tester model CHEK02 and CHEK06 available from SDi. When used properly, 
the canned smoke agent will cause the smoke detector to go into alarm. Re-
fer to the manufacturer’s published instructions for proper use of the canned 
smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer. Misuse or overuse to these products may have long term adverse 
effects on the smoke detector. Consult the canned smoke agent manufacturer’s 
published instructions for any further warnings or caution statements.

[9]DETECTOR CLEANINg PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service. Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[9.1]DETECTOR SENSOR

1. Remove the sensor to be cleaned from the system.
2.  Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place.

3.  Vacuum the screen carefully without removing it. If further cleaning is re-

quired continue with Step 4, otherwise skip to Step 7.

4.  Remove the chamber cover/screen assembly by pulling it straight out.
5.  Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber.

6.  Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place.

7.  Replace the cover using the LEDs to align the cover and then gently pushing 

it until it locks into place.

8. Reinstall the detector.

[9.2]REINSTALLATION

1. Reinstall the detector in its housing.
2. Restore system power. 
3. Perform Detector Check.
4.  Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation.

fIgURE 6. SySTEM wIRINg DIAgRAM fOR D355PL:

HO572-00

COMM. 

LINE (+)

UL/FM LISTED 

CONTROL 

PANEL

1ST 

DETECTOR

IN LOOP

2ND 

DETECTOR

IN LOOP

COMM. 

LINE (–)

COMM. 

LINE

HO112-00

FL-300-000 

4 I56-3255-007R

FL-300-000 

5 I56-3255-007R

[10]SENSOR REPLACEMENT

1. Remove the sensor head by rotating counterclockwise.
2. Pull gently to remove it. 
3.  To replace the sensor head, align the mounting features and rotate clock-

wise into place.

[11] OPTIONAL ACCESSORIES

Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and 

 

RTS451KEY/RTS151KEY.

NOTE: Ensure blue wire always remains connected to RA+ on the field 
connector side of the terminal block.

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED 

OPTION 1 PER UNIT 

H0570-03

Note: If using a RA400Z, the tab should be broken for use with the intelli-
gent duct smoke detector. If using RA100Z, ensure that jumper is removed.

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates 
test of the alarm capability of the duct smoke detector. These accessories pro-
vide the stimulus to initiate an alarm condition at the detector. The D355PL 
duct smoke detector must be reset by the system control panel.

[11.1] OPTION 1: 
REMOTE TEST USINg SENSOR wITh REMOTE TEST CAPABILITy
(wIThOUT A TEST COIL):

A sensor with suffix "R" is available for use inside the D355PL. Suffix "R"  
represents a head with Remote Test Capability. Using this head inside the 
D355PL eliminates the need for a test coil when wired to a RTS451/RTS151/ 
RTS451KEY/RTS151KEY Remote Test Station.

To install the RTS451/RTS151/RTS451KEY/RTS151KEY, using the sensor with  
remote test capability connect the device as shown in 

Figure 9

; wire runs must 

be limited to 25 ohms or less per interconnecting wire. 

NOTE: Resistor assembly must be in place between RA+ and OUT+  
inside the D355PL for Remote Test function to operate.

fIgURE 8. wIRINg DIAgRAM fOR D355PL TO RA400Z/RA100Z:

RTS451/RTS451KEY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

H0633-00

fIgURE 9. RTS451/RTS451kEy/RTS151/RTS151kEy USINg  
SENSOR wITh REMOTE TEST CAPABILITy

[11.2] OPTION 2: REMOTE TEST USINg A TEST COIL:

 

The use of a remote test station requires the installation of an accessory 
coil, part number DCOIL, sold separately.

 

1)   Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2)  Install DCOIL mounting screw
3)  Connect each DCOIL lead to a Test Coil Terminal  
See 

Figure 10

 below for reference.

fIgURE 10. D355PL USINg A TEST COIL

TEST COIL TERMINALS

DCOIL

TEST COIL SCREW

fIgURE 11. wIRINg DIAgRAM fROM D355PL TO RTS451/RTS151/ 
RTS451kEy/RTS151kEy USINg A TEST COIL:

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS451/151,

RTS451/151KEY

REMOTE TEST STATION

LED OPTION

1 PER UNIT

10mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

NOTE: The RTS451/151, RTS451/151KEY test coil circuit requires an 

 

external 24 VDC power supply which must be UL listed.

[11.3] ADDITIONAL MODULE OPTION

The D355PL can also accommodate a relay or control module (sold sepa-
rately) within the power board side of the housing. The relay or control mod-
ule must be listed as compatible to the fire alarm control panel.

Physical Module Mounting 

1)  Remove the breakaway tabs at the four corners of the module
2)   Locate the module at right most corner of the power board. The upper 

left corner mounting hole of the module will align with a screw boss in 
the housing.

3)   Install a #8×

3

8

˝ Plastite screw at the screw boss location

Note: See the corresponding module Installation Instructions for general  
description, control panel compatibility, wiring and ratings.

H0571-07

H0561-01

Summary of Contents for Fire-Lite Alarms Innovair flex D365PL

Page 1: ...ng hazardous condition When sufficient smoke is sensed an alarm signal is initiated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans blowers change over air handling systems etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system The D355PL incorporates a sensor cover tamper f...

Page 2: ...g tubes and 2 C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target C centers If desired drill an additional 156 inch hole at the location of one of the mounting tabs on the lower housing 4 4 Secure the ...

Page 3: ...the housing connection that meets the air flow first Position the tube so that the arrow points into the airflow as shown in Figure 3 Per NFPA sampling tubes over 3 feet long should be supported at the end opposite of the duct detector In ducts wider than 8 feet work must be performed inside the duct to couple the other section of the sampling tube to the section already installed using the inch c...

Page 4: ...ndergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 9 1 Detector Sensor 1 Remove the sensor to be cleaned from the system 2 Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover in place 3 Vacuum the screen carefully without removing it If further cleaning is re quired continue with Step 4 otherwise skip to Step 7 ...

Reviews: