background image

Fire Sentry FS7-130-SX and FS-130-SX2 

 

Controllers

  

Installation  Guide  and  Operating  Manual 
MAN0933_V1_1521-001_Rev E_08-12 

 

 

 

 

 

Page 10

 

SECTION 4: MAINTENANCE  AND  REPLACEMENT 

4.1  Personnel 

Tests must be performed by qualified authorized personnel observing standard safety 
practices. 

WARNING:  Hazardous voltages may be present during testing procedures.  

Serious injury or death may result if personnel fail  to observe 
safety precautions. 

4.2  Controller Faults 

For diagnostic purposes, possible Faults reported by the Controller are shown in the following 
table.  If a Fault is detected, the Controller turns on either the COMM or SYSTEM Yellow Fault 
LED.  Should remedial action fail to clear a Fault condition, call FSC Technical Support. 

Table 1:  Controller Faults 

Fault Message 

ACTION 

SYSTEM Fault 

Controller SYSTEM Fault, such as a broken relay coil or Detector self-
test failure.  If this condition persists, contact FSC for service.  Yellow 
SYSTEM Fault LED turns ON.

 

COMM Fault 

Communications Fault with Detector and Controller

.  

Check wiring for 

broken or crimped cables or loose terminations.  Yellow COMM Fault 
LED turns ON and OFF for the Zone number of the Fault. 

 

SELF TEST 
FAILURE: ZONE 
XX 

The Detector green LED blinks 3 times each 10 seconds. Detector 
indicated by the Zone number has failed its internal optical Self-Test.  If 
this fault persists, the Detector must be returned to the factory for 
service. 

The Detector green LED blinks 4 times each 10 seconds. This fault 
occurs due to leak within Detector housing. Return the Detector to the 
factory for service. 

DETECTOR Faults not reported to Controller 

HIGH 

TEMPERATURE 
FAULT 

The Detector green LED blinks 5 times each 10 seconds.   The 
specified operating temperature range has been exceeded.  The 
Detector must be sent to the factory for service. 

Suggestion: Periodic Maintenance of protected equipment should 
include visual inspection of all detectors. 

MEMORY

 

CORRUPTION 

The Detector green LED blinks 6 times each 10 seconds.  The Detector 
must be sent to factory for service. 

Suggestion: Periodic Maintenance of protected equipment should 
include visual inspection of all detectors. 

Summary of Contents for Fire Sentry FS7-130-SX

Page 1: ... Reserved __________________________________________________________________________ Installation Guide and Operating Manual Fire Sentry FS7 130 SX and FS7 130 SX2 Controllers Controls up to Twelve FS7 2173 Electo Optical Fire Detectors For installation into Fire Control Panels ...

Page 2: ...Fire Sentry FS7 130 SX and FS 130 SX2 Controllers Installation Guide and Operating Manual MAN0933_V1_1521 001_Rev E_08 12 ii ...

Page 3: ...3 Zone Alarm Signal Relays 3 1 3 4 Fault Signal Relay 3 1 3 5 Non Latching Relay Mode 3 1 3 6 Controller s Detector Search 3 1 3 7 Zone Operation 3 1 3 8 FireBusII 4 Figure 1 Model JB 4 Junction Box Enclosure Dimensions 4 Figure 2 FS7 130 SX Controller Enclosure Dimensions 4 Figure 3 FS7 2173 Fire Detector Housing 4 1 4 FSC Junction Boxes 5 SECTION 2 INSTALLATION 6 2 1 Wiring Requirements 6 2 1 1 ...

Page 4: ...anual Detector Test 9 SECTION 4 MAITENANCE AND REPLACEMENT 10 4 1 Personnel 10 4 2 Controller Faults 10 Table 1 Controller Faults 10 4 3 Routine Maintenance and Calibration 11 4 3 1 FS7 2173 Detector 11 4 3 2 FS7 130 SX Controller Module 11 4 4 Detector Faults 11 4 5 Fire Detector and Controller Replacement 11 4 5 1 FS7 2173 Detector Replacement 11 4 5 2 FS7 130 SX Controller Replacement 11 SECTIO...

Page 5: ...ding chemical wet benches The FS7 130 SX2 controller enforces a detector voting regimen as outlined below 1 1 1 Fire Response Stage 1 ALERT This first stage response level is used to signal external audible and visual annunciators and the Detector records an event in the FirePic when the ALERT fire level is reached At this time a manufacturing batch process can be completed if desired and an inves...

Page 6: ...inks ON every 10 seconds to indicate POWER ON rapidly blinks for ALERT and lights up continuously when ALARM is declared The FS7 2173 Detector communicates to the Controller via the 4 wire FireBusII RS 485 interface The FS7 2173 Detector electro optics electronics printed circuit board is housed in a polypropylene leak proof acid resistant enclosure 1 3 FS7 130 SX SX2 Controller The Model FS7 130 ...

Page 7: ...y contacts will open When the Fault is cleared the relay will energize and the contacts will close and the yellow LED will go out For more detailed trouble shooting the SX Software will indicate the Detector which has a Fault condition 1 3 5 Non Latching Relay Mode The controller operates in non latching mode it automatically resets the Fire Signal Relays after 5 seconds if the cause of the condit...

Page 8: ...ine Improper FireBusII operation is indicated by the Controller Fault LED WARNING The Controller requires 24 VDC Under NO circumstances should 120 or 240 VAC be applied to the Controller s input power terminals or any other Controller connection terminals Figure 1 Model JB 4 Junction Box Enclosure Dimensions Figure 2 FS7 130 SX SX2 Controller Enclosure Dimensions 1 00 3 00 3 00 8 00 6 00 150 5 70 ...

Page 9: ...ller The FSC self locking connectors and Junction Boxes are used to eliminate wiring problems and communication Faults and to assure the FSC warranty The Detectors can be daisy chained using the Junction Boxes One Junction Box can accommodate two Detectors The Junction Box at the end of the daisy chain can handle three Detectors The Junction Box closest to the Controller is connected to the Contro...

Page 10: ...the Detector mounting location Make sure the fire threat area is located along the axis of the Detector s Field of View SX2 installation requires both Detectors be within 8 ft of the area to be monitored to support the voting protocol b Choose a fastening method which will secure the detector reliably to the type of material at the enclosure location For example drill custom holes in the mounting ...

Page 11: ...l Field of View viewing angle It is recommended that the Detectors be positioned with the primary fire threat location aimed in the center of the Detector s Field of View Since optical Fire Detectors must see the fire in order to detect it mount the Detectors in locations such as corners and ceilings to avoid line of sight blockage 2 4 2 Mounting FS7 130 SX SX2 Controllers The Controllers are desi...

Page 12: ...nd 4 Red Zone LEDs are OFF 3 3 2 Fault During a Fault condition Yellow LED blinks ON and OFF for COMM communication Faults The COMM Fault LED is the first yellow LED closest to the green POWER ON LED This LED will blink ON and OFF a group of flashes every 5 seconds The number of ON OFF flashes in the group corresponds to the Zone number of the COMM Fault For example if the COMM Fault LED blinks ON...

Page 13: ...self tests are occurring the FS System 7 is still functional and able to detect and alarm to a fire 3 3 4 Manual Detector Test Test the system end to end by activating each Detector separately on the standard SX system SX2 system requires at least two Detectors in a voting group be activated Note Use FSC s Model FT S7 or FS 746 Test Lamps to test each Detector individually WARNING DISABLE RESPONSE...

Page 14: ...M Fault Communications Fault with Detector and Controller Check wiring for broken or crimped cables or loose terminations Yellow COMM Fault LED turns ON and OFF for the Zone number of the Fault SELF TEST FAILURE ZONE XX The Detector green LED blinks 3 times each 10 seconds Detector indicated by the Zone number has failed its internal optical Self Test If this fault persists the Detector must be re...

Page 15: ...le parts within a Detector 4 5 Fire Detector and Controller Replacement 4 5 1 FS7 2173 Detector Replacement 1 Disconnect the Detector s male connector from the Junction Box 2 Make sure there is enough cable slack for removing the Detector 3 Then carefully slide the Detector off its T mount bracket 4 Install a replacement Detector in the inverse order steps 3 2 1 4 5 2 FS7 130 SX SX2 Controller Rep...

Page 16: ...Data B RS 485 COMM B WHITE 5 DC Voltage RED Note COMM as it is used in this document is an abbreviation for Communications Table 3 FS7 130 SX Controller Connector Pinouts J1 Connector Pin Description 1 24 Volts DC IN Supply into Controller 2 24 Volts RETURN Supply into Controller 3 Detector 12 Volts DC 4 Detector 12 Volt DC RETURN 5 Detector Data A RS 485 FireBusII 6 Detector Data B RS 485 FireBus...

Page 17: ...onnector Pin Description 1 Zone 1 Alarm Relay A contact 2 Zone 1 Alarm Relay B contact 3 Zone 2 Alarm Relay A contact 4 Zone 2 Alarm Relay B contact 5 Zone 3 Alarm Relay A contact 6 Zone 3 Alarm Relay B contact 7 Zone 4 Alarm Relay A contact 8 Zone 4 Alarm Relay B contact 9 Master ALERT Relay A contact 10 Master ALERT Relay B contact ...

Page 18: ...Boxes and Male Open Pigtail to interconnect last Junction Box to Controller s plug in screw down terminal strip Each FS7 Teflon cable uses circular self locking plug in connectors with small 3 8 inch diameter constructed of chrome plated brass with gold plated contacts 5 Foot Cable with Male Male connector at each cable end CBMM 5 10 Foot Cable with Male Male connector at each cable end CBMM 10 15...

Page 19: ...9 Detector Test 7 Fault 7 Detector 8 Relay 7 Self curing 7 FirePic 1 Junction Boxes 4 Layout Planning 5 LED Faults 7 Maintenance 8 Mounting Controller Module 6 Detector 6 Multi Spectral Array 1 Normal Operation 7 Power DC 6 Starting up 6 Programming the Controller 6 Relay Fault 7 Replacement Controller Module 9 Detector 9 Setting Up the Controller 6 Stage 1 ALERT 1 Stage 2 ALARM 1 SYSTEM Fault 7 T...

Page 20: ...avastrasse 2 8604 Hegnau Switzerland Tel 41 0 44 943 4300 Fax 41 0 44 943 439 India Tel 91 124 4752700 gasdetection honeywell com Americas Honeywell Analytics Inc 405 Barclay Blvd Lincolnshire IL 60069 USA Tel 1 847 955 8200 Toll free 1 800 538 0363 Fax 1 847 955 8210 detectgas honeywell com Asia Pacific Honeywell Analytics Asia Pacific 508 Kolon Science Valley I 187 10 Guro Dong Guro Gu Seoul 152...

Reviews: