background image

TH5110D NON-PROGRAMMABLE THERMOSTAT

11

69-1712—1

TROUBLESHOOTING

Table 5. Troubleshooting

Symptom

Possible Cause

Action

Display is blank.

Thermostat is not powered.

Check for 24 Vac between Rc and C.

Check that fresh AAA alkaline batteries are 
installed as marked on the battery holder.

Temperature settings do 
not change.

The highest or lowest temperature 
setting was reached.

Temperature setting range:                              
Heating: 40° F to  90 °F (4.5 °C  to 32 °C)                                       
Cooling: 50° F to 99°F (10°C to 37°C)

Heat does not turn on 
(Heat On is solid in the 
display).

Heating equipment failure.

Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not 
present, check the heating equipment to 
find the cause of the problem.

Check for 24 Vac between the heat terminal 
(W) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the heating equipment to find the cause of 
the problem.

Loose or broken wire connection 
between thermostat and heating 
equipment.

Check for 24 Vac between the heat terminal 
(W) and transformer common. If voltage is 
not present, check wire connection (loose or 
broken) between the thermostat and the 
heating equipment.

Cooling does not turn on 
(Cool On is solid in the 
display).

Cooling equipment failure.

Check for 24 Vac at the equipment on the 
secondary side of the transformer between 
power and common. If voltage is not 
present, check the cooling equipment to find 
the cause of the problem.

Check for 24 Vac between the cool terminal 
(Y) and transformer common. If 24 Vac is 
present, the thermostat is functional. Check 
the cooling equipment to find the cause of 
the problem. 

Loose or broken wire connection 
between thermostat and cooling 
equipment.

Check for 24 Vac between the cool terminal 
(Y) and transformer common. If voltage is 
not present, check the wire connection 
(loose or broken) between the thermostat 
and the cooling equipment.

Fan does not turn on in a 
call for heat (electric 
furnace).

Fan Control in Heating (Installer Setup 
Number 3) is set to Gas or Oil Furnace 
(Setting 0).

Set Fan Control in Heating (Installer Setup 
Number 3) to Electric Furnace (Setting 1).

Heat pump puts out cool 
air in the heat mode and 
warm air in the cool 
mode.

Changeover Valve (Installer Setup 
Number 2) is not configured to match the 
changeover required by the installed 
heat pump.

Set Changeover Valve (Installer Setup 
Number 2) to match the changeover 
required by the installed heat pump.

Both the heating and 
cooling equipment are 
running at the same 
time.

The heating equipment is not a heat 
pump but the System Type (Installer 
Setup Number 1) is set to Heat Pump 
(Setting 1).

Set System Type (Installer Setup Number 1) 
to match the installed heating and/or cooling 
equipment.

Heating and cooling wires are shorted 
together.

Separate the shorted heating and cooling 
wires. 

Summary of Contents for FocusPRO TH5110D

Page 1: ...ash Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat Table 1 TH5110D Thermostat description Feature Description Powering Methods Battery only Common wire only Common wire with battery backup System Types Up to 1 Heat 1 Cool Gas oil or electric heat with air conditioning Warm air hot water high efficiency furnaces heat ...

Page 2: ...m ducts Radiant heat from sun or appliances Concealed pipes and chimneys Unheated uncooled areas such as an outside wall behind the thermostat Separate Wallplate from Thermostat 1 Separate the wallplate from the thermostat See Fig 2 Fig 2 Separate wallplate from thermostat Install Wallplate See Fig 3 Mount the thermostat horizontally on the wall 1 Pull the wires through the wire hole on the wallpl...

Page 3: ...prevent drafts from affecting the thermostat NOTES 1 When used in a single transformer system leave metal jumper in place between Rc and R If used on a two transformer system remove metal jumper between Rc and R 2 Common wire is optional when thermostat is used with batteries 3 If thermostat is configured for a heat pump in the Installer Setup configure changeover valve for cool O factory setting ...

Page 4: ...CTOR THERMOSTAT WIRING TERMINALS L2 R C 1 L1 HOT L2 RC C 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 2 3 OPTIONAL 24 VAC COMMON CONNECTION REMOVE FACTORY INSTALLED JUMPER HEAT RELAY M22070 G O B W Y C R Rc L1 HOT FAN RELAY COMPRESSOR CONTACTOR L2 R C 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 2 3 4 OPTIONAL 24 VAC COMMON ...

Page 5: ...LOAD PROTECTION AS REQUIRED 1 2 3 OPTIONAL 24 VAC COMMON CONNECTION 4 4 CONFIGURE SYSTEM TYPE TO HEAT ONLY IN THE INSTALLER SETUP FACTORY INSTALLED JUMPER TR TR POWER TO OPEN AND POWER TO CLOSE MOTOR OR VALVE SERIES 20 B W R THERMOSTAT WIRING TERMINALS M22074 G O B W Y C R Rc L1 HOT L2 R C 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 2 3 OPTIONAL 24 VAC COMMON ...

Page 6: ...llplate Remove the metal jumper between Rc and R Installing Batteries Install two AAA alkaline batteries on the back of the thermostat as marked on the battery holder See Fig 14 NOTE After the thermostat is mounted on the wallplate the thermostat does not require removal from the wallplate to replace the batteries Refer to the enclosed Operating Instructions 69 1713 for more information on the rem...

Page 7: ...nfigure Installer Setup 3 See Fig 18 to review how the thermostat buttons are used during Installer Setup See Table 3 for the Installer Setup Numbers and Settings Fig 18 Review thermostat buttons used for Installer Setup ReplaceBatt Service Needed Setting Cool Inside Fan Auto Cool System M22079 ReplaceBatt Service Needed Done Next M22143 ReplaceBatt Service Needed Done Next M22144 SETTING INSTALLE...

Page 8: ...ling Factory Setting 1 Changeover valve O B terminal energized in heating 3 May not appear See Note b Fan Control in Heating 0 Gas or oil furnace equipment controls fan in heating Factory Setting 1 Electric furnace thermostat controls fan in heating 5 May not appear See Note c Heating Cycle Rate in cycles per hour cph 5 5 cph used for gas or oil furnaces less than 90 efficient Factory Setting 1 1 ...

Page 9: ...appearing ReplaceBatt Service Needed Fan Auto Cool System M22145 ReplaceBatt Service Needed Done Next M22146 SYSTEM STATUS NUMBER SYSTEM TEST NUMBER DONE BUTTON EXITS THE INSTALLER SYSTEM TEST DOWN BUTTON TURNS THE SYSTEM OFF UP BUTTON TURNS THE SYSTEM ON NEXT BUTTON ADVANCES TO NEXT SYSTEM TEST NUMBER Table 4 Installer System Tests System Test Number Test Type System Status Number and Description...

Page 10: ...tartup and after power interruptions If there is a call for cooling or heating during the Minimum Off Time the thermostat flashes Cool On or Heat On a When the Minimum Off Timer expires Cool On or Heat On a appears solid in the display and the compressor and fan turn on ______________ aHeat Pumps only Accessories Replacement Parts 1 Cover Plates see Fig 23 50001137 001 Small Cover Plate 4 5 16 in ...

Page 11: ...he secondary side of the transformer between power and common If voltage is not present check the cooling equipment to find the cause of the problem Check for 24 Vac between the cool terminal Y and transformer common If 24 Vac is present the thermostat is functional Check the cooling equipment to find the cause of the problem Loose or broken wire connection between thermostat and cooling equipment...

Page 12: ... and or cooling equipment System Setting Adjustment Installer Setup Number 12 is set to Auto Changeover Only Setting 2 Set System Setting Adjustment Installer Setup Number 12 to Manual Changeover Setting 0 or Auto Changeover Setting 1 Cannot set the system setting to Cool System Type Installer Setup Number 1 is set to Heat Only Setting 2 or Heat Only with Fan Setting 3 Set System Type Installer Se...

Reviews: