INSTALLER SYSTEM TEST
Use the Installer System Test to test the heating, cooling
and fan.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
1.
Enter the Installer System Test by pressing and
holding down the Up and Down buttons at the
same time for approximately five seconds, until the
screen changes. See Fig. 19.
Fig. 19. Enter Installer System Test.
2.
See Fig. 20 to review how the thermostat buttons
are used during the Installer System Test. See
Table 4 for available Installer System Tests.
Fig. 20. Review thermostat buttons used during
Installer System Test.
Installer System Tests
IMPORTANT
Use the Installer System Test to test the
heating, cooling and fan. The setting you
choose for System Type (Installer Setup
Number 1) may prevent some System Test
Numbers from appearing.
Replace Batt
Service Needed
Fan
Auto
Cool
System
M22145
Replace Batt
Service Needed
Done
Next
M22146
SYSTEM
STATUS
NUMBER
SYSTEM
TEST
NUMBER
DONE BUTTON
EXITS THE INSTALLER
SYSTEM TEST
DOWN BUTTON
TURNS THE
SYSTEM OFF
UP BUTTON
TURNS THE
SYSTEM ON
NEXT BUTTON
ADVANCES TO NEXT
SYSTEM TEST NUMBER
Table 4. Installer System Tests.
System Test Number
Test Type
System Status Number and Description
10
Heating System Test
1
—Heat turns on. When Installer Setup Number
1 is set to 1 or Installer Setup Number 3 is set to
1, the fan turns on immediately.
0
—Heat and fan turns off.
30
Cooling System Test
1
—Compressor and fan turns on.
0
—Compressor and fan turns off.
40
Fan System Test
1
—Fan turns on.
0
—Fan turns off.
70
Thermostat Information
(For reference only)
71
—Software revision number (Major)
72
—Software revision number (Minor)
73
—Configuration identification code (Major)
74
—Configuration identification code (Minor)
75
—Production configuration date code (Week)
76
—Production configuration date code (Year)
Press the Next button to go to the beginning of the Installer System Test or press the Done button to exit the