22
6.2 CONTROL WIRING
Control Wire Recommended Length and Size
Maximum Wire Length
Recommended Wire Size
1-115 ft (1-35 m)
No. 18 AWG
116-185 ft (36-56 m)
No. 16 AWG
186-295 ft (57-89 m)
No. 14 AWG
296-460 ft (90-140 m)
No. 12 AWG
CONTROL PANEL CONNECTIONS
Terminal Numbering Decal
Wire Numbers
A
YELLOW #1 & #2
N1 & N2 - 240 VAC - Sensing for Utility Dropout and Pickup
B
BLUE #3
T1 - Fused 120VAC for Battery Charger (see NOTE)
C
BLACK #3
0 - DC (-) Common Ground Wire
D
RED #4
194 - DC (+) 12 VDC for Transfer Controls
E
WHITE #5
23 - Transfer Control Signal Wire
LARGE NEUTRAL LUG TORQUE SPEC
2/0 TO 14AWG 120 IN-LB (13.56 N-M)
4-6 AWG 35 IN-LB (3.95 N-M),
8 AWG 25 IN-LB (2.82 N-M),
10-14 AWG 20 IN-LB (2.26 N-M)
LARGE GROUND LUG TORQUE SPEC
2/0 TO 14AWG 120 IN-LB (13.56 N-M)
SPRING LOADED CONNECTION POINTS
A
C
D
E
OPTIONAL ALARM
RELAY CONTACTS
(Normally Open)
B*
(*see note below)
Figure 6.1 — Control Wiring (found behind control board)
NOTE: *Wires 23, 194 and 0 must be run through the provided wire shielding provided in the manual bag to separate the low voltage from
the high voltage wires unless the requirement of 300.3(c)(1) of the NEC are met (see the Parts Shipped Loose section).
NOTE: Must be connected to keep battery charged whether unit is running or not.
6.3 MAIN AC WIRING
Figure 6.2 — Main AC Wiring