S3 Series UL Listing Document —
P/N LS10005-051GF-E:D3 3/09/2016
29
Communication Circuits
Installation Wiring
2.10.6 FML-E3 Installation Wiring Diagram
The Fiber-Optic Multi-Mode (FML-E3) is an optional module that provides fiber connectivity to the network.
One FML-E3 is used per a network channel to transmit/receive. Figure 2.10.6.1 illustrates the FML-E3 circuit
board diagram. For system assembly and installation wiring terminal designations, refer to the
FML-E3/FSL-
E3 Installation Instructions, P/N: LS10046-000GF-E
. You can download this document from the Gamewell-
FCI Website (www.gamewell-fci.com).
Figure 2.10.6.1 FML-E3 Circuit Board Diagram
2.10.7 FML-E3 Installation Wiring Terminals
Table 2.10.7.1 lists the FML-E3 installation wiring terminals.
Table 2.10.7.2 lists the FML-E3 switch settings and drive currents.
FML-E3
J2
J1
FIBER-IN
FIBER-OUT
Designation
Description
J1
Connects to the transmitting fiber. (See Note 1)
J2
Connect to the receiving fiber. (See Note 1)
SW1-1
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
SW1-2
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
SW1-3
Sets the optical output power for the transmitting fiber. (See Table 2.10.7.2)
SW1-4
Not used
P1
Plugs on to J5 (Port 1) or J6 (Port 2) of the RPT-E3-UTP.
NOTE:
Use standard ST connector fiber-optic cable, multi-mode, up to 200 µ (optimized for
62.5/125 µ). Signal loss up to 8dB maximum between nodes.
Table 2.10.7.1 FML-E3 Installation Wiring Terminals
SW1-1
SW1-2
SW1-3
Drive Current
OFF
OFF
OFF
10 mA
OFF
OFF
ON
20 mA
OFF
ON
OFF
32 mA
OFF
ON
ON
42 mA
ON
OFF
OFF
54 mA
ON
OFF
ON
64 mA
ON
ON
OFF
76 mA
ON
ON
ON
86 mA
NOTE:
SW1-4 is not used.
Table 2.10.7.2 FML-E3 Switch Settings and Drive Currents