46
S3 Series UL Listing Document —
P/N LS10005-051GF-E:D3 3/09/2016
Section 4: Functionality
4.1 SLP Main Board Features
The SLP-E3 Main Board features shall include the following:
•
An advanced micro-controller system.
•
Sufficient volatile memory for either standalone or networked functionality.
•
Sufficient non-volatile memory for the requisite configuration data and a minimum of 4000 event log
entries.
•
Support for up to two SLC-PM or SLC95-PM Personality Modules.
•
Four Class B / Two Class A NACs.
•
One Municipal Interface (Master Box or Polarity Reversal).
•
One proprietary port for communication with the Network Interface.
•
Resettable or Non-Resettable (AUX B+) Power Outputs.
•
Three Form C Dry Contact outputs, one dedicated to fail-safe Trouble condition, two others user-
programmable (defaulting to Alarm and Supervisory conditions).
•
An isolated RS-232 serial interface for printer output and debugging.
•
An Ethernet (TCP-IP) port for configuration upload/download and other functions.
•
An auxiliary RS-485 port for communication with peripheral devices including displays, switch modules,
and a DACT.
•
A battery charger supporting up to 55 A/H lead-acid batteries.
•
24V (nominal) input connection for system power, including brownout monitoring capability.
•
All necessary control switches, audible and visible indicators for a non-display operation.
Table 4.1.1 lists the SLP-E3 main board functionality.
UL Standard Functions
S3 Functionality
Drift Compensation
Yes
Remote Programming
Yes, via TCP/IP.
Extent/Limitations of Synchronization
Yes
If cross zone or inter unit synchronization is applicable,
show details on the limitations and extent should be included.
S3 Functionality:
The S3 Series panel NACs are synced alike. However, the E3
platform does not provide sync across the network.
NOTE:
A node is a module with an address that resides on the E3
Series ARCNET network.
When a system is intended to provide evacuation signaling to more
than one notification zone, synchronization of the audible emergency
evacuation signal pattern on a notification circuit basis in lieu of a
system basis is acceptable. Show details on the specifics covering the
installation constraints.
S3 Functionality:
When multiple NAC zones are implemented on the same S3 Series
panel, the zones are synced alike from a common on-board sync
generator. One NAC output may be used to control the extended
SNAC booster panels.
Calibrated Detector Sensitivity Testing
For products using an automatic analog smoke detector sensitivity
tests feature. The Installation Instructions should specify the extent of
the range of time intervals between activations of the automatic test
feature.
S3 Functionality:
The Detector Test is automatically initiated every six hours to ensure
the smoke detectors are operating within the sensitivity limits.
Multiple Detection Operation for
Evacuation
Units employing the multiple detector operation described in
55.3.1/3.2. Include guidelines for installing of a minimum of two
detectors in each protected space and to reduce the detector
installation spacing to 0.7 times in the linear spacing in accordance
with NFPA 72.
S3 Functionality:
This is not a panel software function.
Positive Alarm Sequence
Yes
Table 4.1.1 SLP Main Board Functionality