S3 Series UL Listing Document —
P/N LS10005-051GF-E:D3 3/09/2016
55
Section 8: System Configuration
8.1 S3 Series System Listed Service Type Applications
Table 8.1.1 includes the service type applications Listed for the S3 Series System.
8.2 S3 Series System Configuration
Table 8.2.1 lists the minimum S3 Series System configuration.
Type of Service
Model
IDC
Class
Initiating
Device Type
NAC
Class
Type
Signaling
Signal Line
Circuit
Local
SLP
N/A
A, M, WF, SS
A, B
NC, M
Styles 4, 6, 7
Auxiliary
SLP
N/A
A, M, WF
N/A
N/A
Styles 4, 6, 7
Remote Station (PPU)
(See Note 1)
SLP
N/A
A, M, WF
N/A
Polarity
Reversal
Styles 4, 6, 7
Remote Station
(PPU)
(See Note 1)
SLP
N/A
A, M, WF, SS
N/A
DACT, OT
Styles 4, 6, 7
Proprietary (PPU)
SLP
N/A
A, M, WF, SS
N/A
DACT, OT
Styles 4, 6, 7
Proprietary (PPU)
SLP
N/A
A, M, WF, SS
N/A
(See Note 2)
Styles 4, 6, 7
Central Station (PPU)
(See Note 1)
SLP
N/A
A, M, WF, SS
N/A
DACT, OT
Styles 4, 6, 7
Releasing
SLP
N/A
A, M, WF, SS
A, B
M, NC
Styles 4, 6, 7
NOTE 1:
The designated service type used when the product is equipped with the DACT-E3 sub-
assembly for DACT Type Signaling. When equipped with both DACT-E3 and separately Listed
model IPDACT-2 for OT Type Signaling.
NOTE 2:
The designated service type employs peer-to-peer network sharing information. Any
SLC-PM or SLC95-PM node so designated is acceptable as a Proprietary PPU.
Table 8.1.1 S3 Series, Service Type Applications
Accessory/
Sub-Assembly
Part Number
Description Local Remote
Station
(Rev.Pol.)
Proprietary Auxiliary
Remote
Station
(DACT)
Releasing
Service
(Preaction/
Deluge)
SLP
SLP-RB
Smart Loop Panel -
Main Board
Yes
Yes
Yes
Yes
Yes
Yes
SLC-PM
SLC-PM
SLC-PM for System
Sensor Protocol
Yes
Yes
Yes
Yes
Yes
Yes
SLC95-PM
SLC95-PM
SLC95-PM for Apollo
Protocol
Yes
Yes
Yes
Yes
Yes
Yes
LCD-E3
LCD-E3
LCD Display
O
O
O
O
O
O
LCD-SLP
LCD-SLP
LCD Display-SLP
Yes
Yes
Yes
Yes
Yes
Yes
FLPS-7
FLPS-7-RB
Power Supply
Yes
Yes
Yes
Yes
Yes
Yes
RPT-E3-UTP
RPT-E3-UTP Network Repeater
O
O
O
O
O
O
FML-E3
FML-E3
Fiber-Optic Multi-Mode
O
O
O
O
O
O
FSL-E3
FSL-E3
Fiber-Optic Single-Mode
O
O
O
O
O
O
DACT-E3 DACT-E3
Digital Dialer
Communicator Transmitter
No
No
Yes
Yes
Yes
O
ASM-16
1100-0455
Annunciator Switch
O
O
O
O
O
O
ANU-48
1100-0503
Annunciator
O
O
O
O
O
O
LCD-7100
1100-0399
Remote LCD Display
O
O
O
O
O
O
RAN-7100
RAN-7100
Remote LCD Display
O
O
O
O
O
O
NOTE 1:
Y = Yes, N = No, and O = Optional.