S3 Series UL Listing Document —
P/N LS10005-051GF-E:D3 3/09/2016
Installation Wiring
Signaling Line Circuit (SLC) (SLC-PM/SLC95-PM)
2.6.2 SLC-PM Installation Wiring Diagram- System Sensor
Figure 2.6.2.1 illustrates the SLC-PM circuit board diagram. For system assembly and installation wiring ter-
minal designations, refer to the
SLC-PM/SLC95-PM Installation Instructions, P/N: LS10044-000GF-E
. You
can download this document from the Gamewell-FCI Website (www.gamewell-fci.com).
Figure 2.6.2.1 SLC-PM Circuit Board
2.6.3 SLC-PM Installation Wiring Designations
Table 2.6.3.1 lists the SLC-PM installation wiring designations.
2.6.4 SLC-PM Signaling Line Circuit Specifications
Table 2.6.4.1 lists the SLC-PM signaling line circuit specifications.
2.
SLC-PM
J1
TB1
1
4
Designation
Description
Comments
TB1-1
SLC A-
Style 6, Style 7 RETURN (See Note 1)
TB1-2
SLC A+
Style 6, Style 7 RETURN (See Note 1)
TB1-3
SLC B-
Style 4/6, Style 7 OUT (See Note 1)
TB1-4
SLC B+
Style 4/6, Style 7 OUT (See Note 1)
J1
SLC-PM Loop 1
Connects to J5 of the SLP-E3 (See Note 2)
NOTE:
For Style 4, use Terminals B+ and B- only. For Style 6, use terminals B+ and B- and
connect RETURN wiring to A+ and A-. For Style 7 (Class X), wire the same as Style 6 and use
the M500X Isolator Modules per the recommendations as required.
NOTE 2:
Mount the SLC-PM board component side up. Insert the connector pins extending from
J5 on the SLP-E3 to the J1 connector underneath the SLC-PM board. (For additional information,
refer to the Warning and the
SLC-PM/SLC95-PM Installation Instructions,
P/N: LS10044-000GF-E)
.
Table 2.6.3.1 SLC-PM Installation Wiring Designations
!
WARNING: SLC-PM INSTALLATION TO SLP-E3 REQUIREMENT:
INSTALL THE SLC-PM BOARD COMPONENT SIDE UP.
Requirements
SLC-PM Specifications
Circuit Supervision:
Supervised
Circuit Power-Limited:
Class 2 Power-Limited
Nominal Voltage, Frequency:
24 VDC (from FLPS-7 power supply)
Standby Current max. voltage, rated:
0.014 amp
Alarm Current:
0.014 amp
Identify the Manufacturer’s Name, Model
designation for appliances to be used on the circuit
or reference the device compatibility
section/document.
Refer to the Compatibility Addendum to Gamewell-
FCI Manuals, P/N: 9000-0427-L8.
Max. Line Impedance:
40 Ohms and .5 µF line capacitance
Ground Fault Test Impedance:
Zero Ohms
Impedance values and ground faults are
annunciated.
GND FAULT LED or LCD-SLP
Identified by class or by class/style:
One Class A, Style 6, Style 7 or Class B, Style 4
signaling line circuit.
Table 2.6.4.1 SLC-PM Signaling Line Circuit Specifications