These instructions cover the
Mimic LED Driver
Card
(S4-34600) and
Connection converter
(S4-34494), which are designed to be used in
Custom panels.
The
Mimic LED Driver
connects to a
Master Repeat
Card
which in turn connects to a loop circuit of a
Vigilon fire system. Each
Mimic LED Driver Card
can control up to 768 LEDs and this leaflet covers
the connection of up to 2
Mimic LED Driver Cards
.
The
Connector converters
that holds the terminals
for wiring LEDs.
Custom Panel
LED selection
Only use high efficiency
Red
,
Amber
or
Green
LEDs with a
Mimic LED Driver Card
.
"
Do not use
Blue
or
White
LEDs as these are
not suitable for use with the
Mimic LED Driver Card
.
Compatibility
The
Mimic LED Driver Cards
are compatible for use
in Vigilon system where the Control panel has
specific MCC/MCB software, see technical data
section. The
Master Repeat Card
is configured
using the Mimic Configuration Tool.
4188-951_issue 2_01/12_Part 1_Mimic LED driver
1
Data and Installation
Mimic LED Driver Card
S4-34600 & S4-34494
by Honeywell
S4-34600
Mimic LED Driver Card
S4-34494
Connection Converter
26-way
300mm ribbon cable
20-way
200mm Flat flexible cable
B
A
01 L1 02 L2
0C LC
P9
L
N
N
P17
DANGER
BT+
BT
-
+
RS485
0V 24V
-
WRITE PROTECT
BUZZER
DISABLE
P8
DANGER
DO NOT
REMOVE
L
N
P5
FS2
FS4
P16
P4
P2
P1
SW3
PB2
WD1
P14
P7
USB
FS3
2A(QB)
RESET
Mimic Repeat Card
P3
ADDRESS
P2
BOARD
UPSIDEDOWN
ROTATE
P1
P5
IN
P16
P15
P14
P13
P12
P11
P4
OUT
Mimic
LED Driver
Card 2
WARNING
Removal of
cover exposes
live parts
DANGER
P3
ADDRESS
P2
BOARD
UPSIDEDOWN
ROTATE
P1
P5
IN
P16
P15
P14
P13
P12
P11
P4
OUT
Mimic
LED Driver
Card 1
Connector
Converter 6
Connector
Converter 1
LED Bank 1 (768 LEDs)
LED Bank 2 (768 LEDs)
2 4 6
10
8
12 14 16 18 20 22
26
24
1 3
5
9
7
11 13 15 17 19 21
25
23
2 4 6
10
8
12 14 16 18 20 22
26
24
1 3
5
9
7
11 13 15 17 19 21
25
23
2 4 6
10
8
12 14 16 18 20 22
26
24
1 3
5
9
7
11 13 15 17 19 21
25
23
2 4 6
10
8
12 14 16 18 20 22
26
24
1 3
5
9
7
11 13 15 17 19 21
25
23
Maximum of up to
1536 LEDs can be
controlled with
2 Mimic LED Driver
Cards
01 L1 02 L2
0C LC
P9
L
N
P16
Custom Panel
Backbox
Door
20 way
cable
26 way
cable
Vigilon device loop
To mains fused spur unit
Address
P3
Address
P3
B
+
+
-
-
No link fitted
One link fitted
*
*
*
No links are fitted here
for this application.
Links set LED
board orientation.
A
B