background image

How to link Mimic LED ‘Shapes’ to system events

Each used LED shape must be linked with a system event, such as:

¨

Device fire

¨

Device fault

¨

Channel fire

¨

Channel fault

¨

Zone fire

¨

Zone fault

¨

Card fire

¨

Card fault or

¨

Supervisory Command Build.

Below is a typical example that shows how a shape can be linked to a zone:

For full information on configuration see the instructions supplied with the

Mimic Configuration tool.

Test

Test the Custom panel and ensure it gives the correct indication for the configured Vigilon System event.

Commissioning information

Mimic LED Driver Card

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK

Website: www.gent.co.uk

Tel44 (0) 116 246 2000

Fax (UK): +44 (0)116 246 2300

2

4188-951_issue 2_01/12_Part 2_Mimic LED driver

by Honeywell

Drag and drop an LED ‘Shape’ onto the
a system event in the system tree. This
example shows

being dropped

onto

so the two are linked.

Shape 5

Zone 5,

The LED Shape

here is linked to

.

So when

has a fire event then the LED connected

to

terminals

and

will be lit (On).

Note also the

is associated with

IDC Connector

on the

5 P16_26_8

Zone 5 - Fire

Zone 5

26

8

P16

Connection Converter

Connection Converter

Mimic LED Driver Card.

Summary of Contents for GENT Mimic LED Driver Card

Page 1: ...rd S4 34494 Connection Converter 26 way 300mm ribbon cable 20 way 200mm Flat flexible cable B A 01 L1 02 L2 0C LC P9 L N N P17 DANGER BT BT RS485 0V 24V WRITE PROTECT BUZZER DISABLE P8 DANGER DO NOT REMOVE L N P5 FS2 FS4 P16 P4 P2 P1 SW3 PB2 WD1 P14 P7 USB FS3 2A QB RESET Mimic Repeat Card P3 ADDRESS P2 BOARD UPSIDEDOWN ROTATE P1 P5 IN P16 P15 P14 P13 P12 P11 P4 OUT Mimic LED Driver Card 2 WARNING...

Page 2: ...r the earth is connected to the Custom panel or not Do not use any part of building structure for earthing Mains supply The mains supply to the Custom panel must be via an unswitched 5A fused spur unit A disconnect device must be provided to disconnect both poles and must have a minimum gap of 3mm The disconnect device should be available as part of the building installation and must be easily acc...

Page 3: ...end of the 26 way ribbon cable to the IDC header on the Mimic LED Driver card P11 and the other end to a Connection converter The Mimic LED Driver card can accommodate up to 6 26 way ribbon cable for wiring LEDs via 6 Connection converters 4188 951_issue 2_01 12_Part 1_Mimic LED driver 3 Mimic LED Driver Card Data and Installation P13 P4 OUT P5 IN Master Repeat Card P4 OUT P5 IN Mimic LED Driver C...

Page 4: ...itable recycling centre At the end of their useful life the packaging product and batteries should be disposed of via a suitable recycling centre and in accordance with national or local legislation 2 4 6 10 8 12 14 16 18 20 22 26 24 1 3 5 9 7 11 13 15 17 19 21 25 23 LED Ref LED Ref LED Ref LED Ref LED Ref LED Ref LED Ref LED Ref 1 26 8 9 25 8 17 24 8 25 23 8 33 22 8 41 21 8 49 20 8 57 19 8 2 26 7...

Page 5: ...tion converters associated with a Mimic LED Driver Card 4188 951_issue 2_01 12_Part 2_Mimic LED driver 1 Commissioning information Mimic LED Driver Card S4 34600 S4 34494 by Honeywell Do not alter these settings as they are pre defined in the LED Driver template file 7 P16_24_8 Shape number 7 Related to IDC Connector P16 on the Mimic LED Driver Card IDC connector P16 is ribbon cabled to Connection...

Page 6: ... reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1TN UK Website www gent co uk Telephone 44 0 116 246 2000 Fax UK 44 0 116 246 2300 2 4188 951_issue 2_01 12_Part 2_Mimic LED driver by Honeywell Drag and drop an LED Shape o...

Reviews: