background image

How to wire the

BACnet Gateway

board into the Vigilon Compact Network Node

The

BACnet Gateway

connects to GENT EN54 Vigilon Fire Alarm network via RS232 serial port and

connects to

BACnet

front end via RJ45 Ethernet connector. To wire the

BACnet Gateway

board inside a

Vigilon Network node follow illustrated steps

y

to

{

.

How to download the Configuration tool

A configuration tool is a programming utility used to configure the

BACnet Gateway.

The configuration tool requires Windows® 2000, 98, NT version 4 or XP.

A

Vigilon BACnet Support file.zip

contain the Configuration tool for configuring the

BACnet Gateway

Board. The zip file can be downloaded from

GENT Expert

, website address:

http://gentexpert.co.uk/

Once the file is downloaded you will need to unzip the file and extract the files within for use.

How to configure the

GENTGW.ini

file

The

GentGW.ini file

is held in the flash of the

BACnet Gateway.

The file holds data of the Gateway BBMD

device, Event Properties, Gateway IP Configuration, Gateway Properties and Time zone. The file is modified
by the GENT Gateway Configuration tool and saved changes can be uploaded to the

BACnet Gateway card

.

BACnet Gateway card

"

The

BACnet Gateway

card leaves the factory initilised for the first time.

The

BACnet Gateway

will have the following default settings:

¨

Gateway IP address: 10.1.6.253

¨

Routing IP address: 10.1.6.2

¨

Subnet mask: 255.255.255.0

¨

BBMD IP address: 10.1.6.2

¨

BBMD Subnet mask: 255.255.255.0 (Gateway registers as a foreign device)

BBMD - BACnet Broadcast Management Device.

Installation and Configuration

Vigilon BACnet Gateway

2

4188-970_issue 2_08/11_BACnet

J14

J7

J6

J8 ENET

J13

USB A

USB B

+
24V OUT
-

NC

C

NO

PB15

PB6

24V

B

A

0V

TX1 RX1 0V TX2 RX2

PB14

L1 0V L2 0V

Main Control Board

BACnet Gateway Board

Vigilon Network Node

If required fit the surge protector

device in-line with the Ethernet

cable, see instructions supplied
with the surge protector.

p

Ethernet RJ45

100 ohms 100m max.

24V power supply

RS232

NUP A

NUP B

Ethernet
Network

Configuration tool
on PC

+

24V IN

-

Summary of Contents for GENT VIG-BNG

Page 1: ... TX NFN B ACTIVE LINK DATA ENET PWR PWR WDT PROGRAM HS GW EMPCA REVB 1 x BACnet Gateway Board 1 x Board Carrier 4 x Board Spacers for BACnet Board 1 x Red and black wires for power supply 1 x Surge Protector for RJ45 1 x 1A fuse 2 x Board Spacers for Board Carrier EBI BACnet Card 1 x Cable assembly RS232 1 x Spare parts PB15 PB6 24V B A 0V TX1RX1 0V 24V FS3 BATT3 PB15 PB6 PB9 P2 CARD 1 IC3 IC16 PO...

Page 2: ...ile holds data of the Gateway BBMD device Event Properties Gateway IP Configuration Gateway Properties and Time zone The file is modified by the GENT Gateway Configuration tool and saved changes can be uploaded to the BACnet Gateway card BACnet Gateway card The BACnet Gateway card leaves the factory initilised for the first time The BACnet Gateway will have the following default settings Gateway I...

Page 3: ... IP configuration values to site specific requirements The values shown are those set during initialisation n Enter the business name in Gateway location o Save the settings made to GENTGW ini file The Network number and Gateway ID has to be different if two Gateways are using the same BACnet client and subnet d Save the changes made to the configuration e Set the IP address of the BACnet Gateway ...

Page 4: ...ions are given at the card Installation and Configuration Vigilon BACnet Gateway Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1TN UK Website www gent co uk Telephone 44 0 116 246 2000 Fax UK 44 0 116 2...