Password or PIN code

"

The terms

Password, PIN (Personal

Identification Number), Usercode and Access code

mean the same and are used interchangeably.

A password restricts access to the controls available to the
user at the Repeat panel.

There are four access levels to the controls.

¨

The

Access

level 1

controls only allows

cycling through of multiple fire events
messages on the screen using the two
buttons on the outer door.

¨

Access level 2a

is for the CUSTOMER. Here

the person responsible for the system can
access the 'essential controls' by opening the
panel outer door using a key

¨

Access level 2b

is for the CUSTOMER. Here

the person responsible for the system can
access essential controls and some
configuration menus using the panel door key
plus a customer PIN.

¨

Access level 3

is for the ENGINEER. Here

the person responsible for the system can
access essential controls and all system
menus using the panel door key plus Engineer
PIN.

¨

Daily PIN

There is another PIN that changes daily,
which is available to the servicing
organisation. This daily PIN provides the same
access to controls as the Engineers' PIN. The
daily PIN is only used when the Engineer's
PIN is not known.

"

Always make a note of the Customer and

Engineering PINs once they are created. Ensure the
Customer PIN is passed on to the person responsible
for the fire alarm system on the site.

How to create an Engineer PIN

"

All Vigilon panels leave the factory with no Engineer PIN code
(Access level 3 code). Therefore, on first power up there is an
open access to all the Access level 3 menus.

The menu options under the Engineer PIN provides access to

access

level 3

controls that can alter the configuration of the system.

To create or change an existing Engineer PIN:
(You will need to be at Access level 3 if an Engineer PIN is already
set up.)

¨

Press the

Menu On/ Off

button and select

[Test/Eng]

->[UserCode]# ->

then momentarily press

<etc>

to

select

[Config] -> [New Pass]

and then type a new

PIN or change an existing PIN and press the Enter
key.
# - will appear if a PIN is already setup.

¨

It is recommended that the PIN is at least 4 numbers
and no greater than 15 numbers and letters in the
password code.

How to change the Customer PIN

"

This repeat panel automatically sets up a

FACTORY DEFAULT CUSTOMER PIN: 2 2 2 2, that is after
an Engineer PIN is made active.

The Customer PIN provides access to access level 2 restricted menu
options that cannot alter the configuration of the system. To change a
Customer PIN:

You will need to be at Access level 2.

¨

Press the

Menu On/Off

button and then

[Test/Eng]

-> [UserCode] ->

enter the existing Customer PIN

and select

[Enter],

select

[New Pass]

and then type

a PIN of less than 15 characters in length and press
the Enter key.

¨

It is recommended that the PIN is at least 4 numbers
and no greater than 15 numbers for Vigilon

compact

and Vigilon Compact VA panels. The Vigilon panels
can use numbers and letters in the password code.

How to erase a PIN

The Engineer or Customer PIN can be erased. To erase the PIN of
either Customer or Engineer level you will need to be at the
respective access level.

¨

Press the

Menu On/Off

button and then

[Test/Eng]

-> [UserCode] ->

enter the existing Customer

PIN/Engineer PIN and select

[Enter],

select

[New

Pass]

and then just press the Enter key, this will

erase the PIN. If the Engineer PIN is erased then
Customer PIN is also erased giving open access to all
the menus.

Commissioning information

Vigilon Repeat panel (EN/BS)

2

4188-839_issue 7_08/12_pt2_EN/BS Repeat_inst

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for GENT VIG-RPT-72

Page 1: ...o 45ºC Relative humidity Non condensing Up to 90 temperature 5 C to 45 C Battery 12V 7Ah sealed lead acid Mains operating voltage 230V 15 10 50 60Hz Rated Current 0 2A Emission BS EN61000 6 3 2001 Immunity BS EN50130 4 1996 Part 4 LVD BS EN 60950 2006 Ingress protection IP31 estimated Colour Door Pantone 422 Back box Graphite Grey RAL 7024 Controls with door closed Access level 1 Next and Previous...

Page 2: ...o terminal block P9 on the Master Repeat Card fit battery lead supplied in the spares to connector P5 on Master Repeat Card connect the loop cables to terminal block P16 on the Master Repeat Card connect the 40 way ribbon cable to the Master Repeat Card connector P2 and the other end to Display Key Card on the top right edge connector P1 connect the 20 way ribbon cable to the Master Repeat Card co...

Page 3: ...e Loop COM Master Repeat Card 01 L1 02 L2 0C LC P9 L N N P17 DANGER BT BT RS485 0V 24V WRITE PROTECT BUZZER DISABLE P8 DANGER DO NOT REMOVE L N P5 FS2 FS4 P16 P4 P2 P1 SW3 PB2 WD1 P14 P7 USB FS3 2A QB RESET DANGER WARNING Removal of cover exposes live parts mains electrical supply Loop OUT Previous Next Spur Connection XXXXX Fire Alarm System GENT 2007 Designed to EN54 Pt 2 4 Panel healthy 15 45 1...

Page 4: ...control buttons must always be left in an enabled state with the control buttons link fitted At the end of their useful life the packaging product and batteries should be disposed of via a suitable recycling centre and in accordance with national or local legislation Do not dispose of with your normal household waste Do not burn WEEE Directive At the end of their useful life the packaging product ...

Page 5: ...r sounds Cancel the buzzer using the local Cancel buzzer button Test functions When operating the SOUND ALARMS button it will activate the alarm sounders in the system Display test to ensure all LEDs are working Sound Alarms Silence Alarms Display of Fire events Reset Operation of U1 U4 Function keys as configured at the control panel Verify as configured at the control panel 4188 839_issue 7_08 1...

Page 6: ...configuration of the system To create or change an existing Engineer PIN You will need to be at Access level 3 if an Engineer PIN is already set up Press the Menu On Off button and select Test Eng UserCode then momentarily press etc to select Config New Pass and then type a new PIN or change an existing PIN and press the Enter key will appear if a PIN is already setup It is recommended that the PI...

Page 7: ...ith Mk4 MRC Menu map Control E C Q Key E Enter C Cancel Q Quit Verify etc Params 0 3 E C Q Timeslot etc Params 1 16 Delay On Params HH MM SS On E C Q Off Off DelayBlk Params 1 16 Delayed E C Q Params MM SS 0 10min End E C Q Stop Group EN BS EN BS Option for BS Repeat panel only Option for EN Repeat panel only Sector Build Params 1 255 E C Q Aux Rly Params 1 2 E C Q Params 1 32 E C Q Enable Disable...

Page 8: ... Params 0 100 Signal C Q E Params 16 100 C Q E Params 0 255 Params 1 100 C Q E etc State enable Params 1 8 Params 0 15 C Q E Params 0 15 State disable TimeBlok etc Voice Tone number Set Up Loop Params 1 207 Device It is important to back up the data at the main control panel following any changes using the in Setup menus at the repeat panel Menus accessible with panel door open and AL2 password Ac...

Page 9: ...8 C Q E N C P R 1 100 Loop Params 1 207 E Params 0 15 Q C E E Params C Q 1 207 Loop Params Fault Disable Exceptions Sub Faults HistFire etc etc Warning Device 1 4 1 32 Params Loop Params 1 255 E C Params Q MCP IO Line Device Device Sector Card etc Params 1 207 C Q E 1 8 Device Params Q E etc Active Historic Events Label UserCode TimeAvg Status etc Loop Map Control Set Up Info Test Eng EN BS Repeat...

Reviews: