Appendix A: Ademco Contact ID Format Event Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format.
A.1 Transmission Format Between DACT and Receiver
The transmission string for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
where
SSSS= Four digit Subscriber ID Account Code
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code
GG= Group number
CCC= Zone number
Notes:
1.
18
, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the alarm and trouble
report.
2.
GG
Group Number is fixed at '00' and cannot be changed.
3.
CCC
for Zone Number is transmitted as ‘001’ for zone 1 up to ‘010’ for zone 10
A.2 Ademco Contact ID Typical Printout
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID
Reporting Structure follows:
Notes:
1.
11
is an example of a Receiver/Line Card, showing which receiver and line card the message was transmitted to.
2.
Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an
E
for New Event or R for New Restore.
Time
Date
Rcvr/Line ID
SSSS
QXYZ
GG
CCCC
11:28
03/25
11
7777
E110
00
C001 - general fire alarm on zone one
11:28
03/25
11
7777
E111
00
C002 - smoke detector alarm on zone two
11:28
03/25
11
7777
E380
00
C003 - fault on zone three
11:28
03/25
11
7777
E570
00
C009 - Zone nine disabled
11:28
03/25
11
7777
R110
00
C001 - Zone one alarm restored
11:28
03/25
11
7777
R111
00
C002 - smoke detector zone two restored
11:28
03/25
11
7777
R380
00
C003 - zone three fault restored
11:28
03/25
11
7777
R570
00
C009 - zone nine reenabled
11:28
03/25
11
7777
E158
00
C006 - high temperature, zone six
11:28
03/25
11
7777
E151
00
C007 - gas detected, zone seven
EVENT
MESSAGE
Medical Alarms - 100
100 Medical
EMERG - Personal Emergency - #
101 Pendant Transmitter
EMERG - Personal Embergency - #
EVENT CODE CLASSIFICATIONS
100
ALARMS
200
SUPERVISORY
300
TROUBLES
400
OPEN/CLOSE
REMOTE ACCESS
500
DISABLES/
BYPASSES
600
TEST/
MISC.
Medical
Fire
Panic
Burglary
General
24 Hour
Fire
System
Sounder/Relay
System Peripheral
Communication
Protective Loop
Sensor
Open/Close
Remote Access
Access Control
System
Sounder/Relay
System Peripheral
Communication
Test
GF505 & GF510 Manual —
P/N 53164:B5 6/12/2018
1
0
3