Components
Product Description
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wiring interface connectors. Optional
modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
•
FLPS-7 for the GF505 & GF510
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp
Hours). Also available is an optionaltrim-ring (TR-CE).
Batteries
The cabinet provides space for two 18 Amp Hour batteries. Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B)
Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the GF505 and to J7 on the GF510. Note that two
Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a
disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condi-
tion if no alarm condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
GFANN-80 LCD Annunciator
The GFANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display and provides remote
RESET, SILENCE, ACKNOWLEDGE, and DRILL.
GFANN-LED Annunciator Module
The GFANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. GFANN-LED module is
installed in dress panel for Canadian version.
GFANN-RLY Relay Module
The GFANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cabinet.
Battery Box
BB-55F battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control
panel cabinet, centered to the main circuit board.
Battery Charger
FCI-CHG-120 Battery Charger
The FCI-CHG-120 is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled,
through software programming, when using the FCI-CHG-120. The batteries and charger can be housed in the BB-55F battery box
which can be mounted up to 20 feet away from the control panel. Note that when using a BB-55F for housing the charger and batteries
greater than 26AH, multiple BB-55Fs are required. Refer to the
FCI-CHG-120 Manual
for additional information.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal
computers (PC), running Windows
®
XP (or newer). FACP program files can also be created and stored on the PC and then downloaded
later to the control panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help
file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of
the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster)
modem.
Important:
Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote
Download” on page 98). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the
remote download option.