Operating Instructions
Read Status
Pressing
1
while viewing the Print Screen allows the user to print the History file which will detail all of the system activities since the
file was last cleared from memory.
Pressing
2
while viewing the Print Screen allows the user to print the Walktest log which will detail all of the system activations during
walktest since the log was last cleared. Refer to “Walktest” on page 82 for additional information on the display.
Pressing
3
while viewing the Print Screen will exit the Print operation.
4.19.9 ANN-BUS
Pressing
3
while viewing Read Status Screen #3 will display the settings for the ANN-BUS options as
shown in the following screens:
ANN-BUS Screen #1 indicates whether the ANN-BUS is enabled (Yes/No).
Pressing
1
while viewing ANN-BUS Screen #1 will display BUS Module addresses 1-8 and the devices, if any, located at those
addresses.
Pressing
2
while viewing ANN-BUS Screen #1 will display the printer settings for the printer connected to the FACP. This information
includes:
•
Serial or Parallel printer
•
Printer Supervision (Yes or No)
•
Off-line Timer setting
•
Baud Rate
•
Data Bits
•
Parity
•
Stop Bits
Pressing
1
while viewing ANN-BUS Screen #2 will display the programmed options for the GFANN-80 devices connected to the ANN-
BUS. These include Piezo enable/disable, Lock enable/disable and which buttons/keys on the annunciator are enabled/disabled.
Pressing
2
while viewing ANN-BUS Screen #2 will display the zone programming for each GFANN-RLY relay.
Pressing
3
while viewing ANN-BUS Screen #2 will display the zone, if any, that has been assigned as the All-Call Zone.
Note the the ANN-AUDIO option is not presently available.
4.19.10 Central Station
Pressing
1
while viewing Read Status Screen #4 will display the following screens:
Central Station Screen #1 indicates whether the Central Station Reporting is enabled or disabled and if the Reports will be sent to one or
both the Primary and Secondary Central Station phone numbers. Central Station Screen #2 provides information on the Primary and Sec-
ondary Central Station programming which includes:
•
Test Time Interval
•
Account Code
•
24 Hour Test Time
•
Phone Number
•
Communication Format
•
Event Codes
This screen also displays the Call Limit for each unique DACT trouble call within a 24 hour period
4.19.11 Phone Line
Pressing
1
while viewing Read Status Screen #4 will display the following screen:
The second and third lines of this screen indicate that both the Primary and Secondary phone lines have been configured for touchtone
dialing operation.
READ STATUS
1=HISTORY
2=PRINTER
3=ANN-BUS
Read Status Screen #3
ANN-BUS
BUS ENABLED NO
1=BUS MODULES
2=ANN-S/PG OPTIONS
ANN-BUS
1=ANN-80 OPTIONS
2=ANN-RLY OPTION
3=ANN-AUDIO OPTIONS
ANN-BUS Screen #1
ANN-BUS Screen #2
READ STATUS
1=CENTRAL STATION
2=PHONE LINES
3=SERVICE TERMINAL
Read Status Screen #4
CENTRAL STATION
REPORTING YES
REPORT STYLE BOTH
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
0
Central Station Screen #2
PHONE LINES
PRIMARY
TCH TNE
SECONDARY TCH TNE
3=SUPERV PHONE LINE