background image

GATEWAY (GW-1000-WE/GW-1000-NWE)

31-00426 | Rev.10-20

2

CONTENTS

General Safety Information ............................................... 3

Technical Data ....................................................................... 4

Electrical Data ............................................................................... 4

Power Consumption  ................................................................... 4

Current Consumption  ................................................................ 4

Operational Environment  ......................................................... 4

Default IP Address  ....................................................................... 4

Standards ........................................................................................ 4

Interfaces ............................................................................... 5

Main LED ......................................................................................... 6

Ethernet LEDs  ............................................................................... 7

Reset Button  .................................................................................. 8

Communication Baud Rates  ................................................... 8

Connection to Honeywell Forge ............................................. 8

Connection to MultiTech LoRaWAN Hub ........................... 8

Small and Medium Building 

Administrator Supervisor Dashboard .................................. 8

Honeywell Connect Mobile App  ............................................. 8

POWER SUPPLY ................................................................... 8

Transformers .................................................................................. 8

Switch Mode Power Supply ...................................................... 9

Fusing ............................................................................................... 9

Wiring and Set-up  ................................................................ 9

General Safety Considerations ................................................9

Wiring Terminals  ...........................................................................9

Connecting Power Supply  .........................................................9

Earth Grounding  ...........................................................................9

WIRING CONNECTIONS ..................................................... 10

Gateway to MultiTech LoRaWAN hub connection ...........10

Wireless Connectivity .......................................................... 11

Connectivity Frequency Range  ...............................................11

General Information  ....................................................................11

Dimensions ............................................................................. 12

GW-1000-WE/GW-1000-NWE Gateway  ............................12

Appendix: Earth Grounding ............................................... 13

Gateway and SELV ........................................................................13

Gateway and EN60204-1 ..........................................................13

Functional EMC Grounding ......................................................13

Gateway Part Numbers ....................................................... 14

Accessories Part Numbers ........................................................14

Remote Antenna Part Numbers ..............................................14

Hub and Sensors ...........................................................................14

Summary of Contents for GW-1000-NWE

Page 1: ...INSTALLATION INSTRUCTIONS SMB Gateway GW 1000 WE GW 1000 NWE ...

Page 2: ...n conformance FEATURES Integrated with Small and Medium Building Administrator Supervisor Dashboard built on Honeywell Forge cloud platform Configurable via the Honeywell Connect Mobile app Integrated with Honeywell Thermostat TC500A N TC500A W and Honeywell Smart IO IO 10MIXR NWE IO 10MIXR WE via BACnet secured Compatible with MultiTech LoRaWAN hub Compatible with R718A R718CT and R718G sensors S...

Page 3: ... Power supply 24 Vac dc RS485 Interface 3 Terminals 2 CH3 for RS485 interface 3 CH3 for RS485 interface 3 GND3 GND3 for RS485 interface 3 RS485 Interface 2 Terminals 3 CH2 for RS485 interface 2 CH2 for RS485 interface 2 GND2 GND2 for RS485 interface 2 RS485 Interface 1 Terminals 4 CH1 for RS485 interface 1 CH1 for RS485 interface 1 GND1 GND1 RS485 interface 1 LED 5 Tx1 LED green Transmit and recei...

Page 4: ... 5 Tx3 LED green Transmit and receive indication for RS485 interfaces 1 to 3 Rx3 LED green 6 Main LED Indicates the operational status of the Gateway RJ45 Interface 7 Ethernet 1 Dedicated to Internet Cloud connectivity 10 100 1000BASE T 8 Ethernet 2 Dedicated to MultiTech LoRaWAN hub 10 100 1000BASE T SMA Terminal 9 For Wi Fi and Bluetooth antenna Antenna for both Wi Fi and Bluetooth 802 11a b g n...

Page 5: ...otocol version IEEE 802 3 Testing Electrical Components IEC68 Certification UL60730 1 UL916 EN 60730 1 EN 60730 2 9 FCC Part15 Subpart B CAN ICES 3 B NMB 3 B BQB RoHS II REACH System Transformer The system transformer s must be safety isolating transformers according to IEC 61558 2 6 In the U S A and Canada NEC Class 2 transformers must be used Table 6 Operating Environment Ambient Operating Tempe...

Page 6: ...t 100 ft Supported type of Wi Fi connections Wi Fi Access Point Providing access point to IO 10MIXR WE IO 10MIXR NWE Smart IO and TC500A N Commercial Thermostat devices Table 8 Gateway Parameters Max number of points 3000 Max trend retention 2 days 1 min samples Max number of alarms retained 70000 Records History push Per Minute GW OTA Upgrade check Once in 4 hours Devices OTA Upgrade check Once i...

Page 7: ...nded Terminal Covers Large Pack Quantity of 4 ANT REM Remote Antennas with adhesive magnetic foot for wireless communication 1 5 meter 4 9 feet cable length for remote mounting of the antenna Pack Quantity of 4 Ferrite Ring Part Number ZCAT3035 1330 BK Manufacture TDK GW ANT LOC Local Antennas optional not included in the kit MPN ANT DB1 LCD SMA Manufacturer LINX Technologies Pack Quantity of 4 Ta...

Page 8: ...0100 or EN 60204 1 for earth grounding Use only accessory equipment that comes from or has been approved by Honeywell It is recommended that devices be kept at room temperature for at least 24 hours before applying power This is to allow any condensation resulting from low shipping storage temperatures to evaporate The GW 1000 WE GW 1000 NWE Gateway must be installed in a manner e g in a lockable ...

Page 9: ...height of max 45 mm It is suitable for panel rail mounting on 35 mm standard panel rail both horizontal and vertical rail mounting possible The GW 1000 WE GW 1000 NWE is used for the purpose of building HVAC control and is suitable for use only in non safety controls for installation on or in appliances Table 12 Safety Information as per EN60730 1 Electric Shock Protection PELV Pollution Degree Po...

Page 10: ...visor Dashboard 8 Honeywell Connect Mobile App 8 POWERSUPPLY 8 Transformers 8 Switch Mode Power Supply 9 Fusing 9 Wiring andSet up 9 General Safety Considerations 9 Wiring Terminals 9 Connecting Power Supply 9 Earth Grounding 9 WIRINGCONNECTIONS 10 Gateway to MultiTech LoRaWAN hub connection 10 WirelessConnectivity 11 Connectivity Frequency Range 11 General Information 11 Dimensions 12 GW 1000 WE ...

Page 11: ...vant technology not readily available to average consumer Only a person professionally trained in the technology is competent This device is not directly marketed or sold to general public Safety Information as per EN60730 1 The GW 1000 WE GW 1000 NWE gateway is intended for residential commercial and light industrial environments The GW 1000 WE GW 1000 NWE gateway is an independently mounted elec...

Page 12: ...ity non condensing Ambient Storage Temperature 28 9 to 70 C 20 to 158 F Ambient Storage Humidity 5 to 95 relative humidity non condensing Vibration Under Operation 0 024 double amplitude 2 to 30 Hz 0 6 g 30 to 300 Hz Dust Vibration According to EN60730 1 RFI EMI Residential commercial and light industrial environments MTBF Mean Time Between Failure 11 5 years Table 6 Default IP Address IP Address ...

Page 13: ...er supply 24 Vac dc RS485 Interface 3 Terminals 2 CH3 for RS485 interface 3 CH3 for RS485 interface 3 GND3 GND3 for RS485 interface 3 RS485 Interface 2 Terminals 3 CH2 for RS485 interface 2 CH2 for RS485 interface 2 GND2 GND2 for RS485 interface 2 RS485 Interface 1 Terminals 4 CH1 for RS485 interface 1 CH1 for RS485 interface 1 GND1 GND1 RS485 interface 1 LED 5 Tx1 LED green Transmit and receive i...

Page 14: ... expansion modules 24V0 FGND GND for RS485 interface 4 for RS485 interface 4 RJ11 Interface 11 for RS485 interface 5 for RS485 interface 5 output 5Vdc GND USB Interface 12 Micro USB port to connect with laptops mobile and tablets 13 USB Type A port Reset Button 14 Reset button to reset the device to factory default Table 8 Gateway Terminals Continued Type Legend Signal Comment Table 9 Main LED Pat...

Page 15: ...t interfaces 1 and 2 Case LED Behavior Meaning Remedy 1 Yellow LED is ON steadily Ethernet is working with connectivity up to 100Mbps If communication problems persist then check the green LED See Case 3 and Case 4 given below 2 Yellow LED is OFF If the green LED is ON or flashing then Ethernet is working with connectivity up to 10Mbps If the green LED is OFF then Ethernet is disconnected Connect ...

Page 16: ...000 WE GW 1000 NWE gateways to the same transformer Transformers Honeywell Transformers A transformer can power the GW 1000 WE GW 1000 NWE gateway When determining total current consumption and selecting the appropriate transformer take into account the number of connected modules accessories and field devices NOTE In Europe system transformer s must be safety isolating transformers according to I...

Page 17: ...connection WARNING Risk of electric shock or equipment damage Do not touch any live parts in the cabinet Disconnect the power supply before making connections to or removing connections from Gateway terminals Do not use spare terminals as wiring support points Do not reconnect the power supply until you have completed the power supply CAUTION Observe the precautions for handling electrostatic devi...

Page 18: ...o not connect the MultiTech LoRaWAN Hub to Ethernet 1 If connected to Ethernet 1 mistakenly then restart the MultiTech LoRaWAN Hub before connecting to Ethernet 2 TX 5V GND Isola on Barrier RX 5V_ISO GND_ISO RS485 RS485 24V 24V0 FGND CH1 CH1 GND1 GW 1000 WE GW 1000 NWE Ethernet 1 Ethernet 2 Mul Tech LoRaWAN Hub Ethernet 5VDC ...

Page 19: ... RF exposure compliance FCC Class B Statement NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used...

Page 20: ...GATEWAY GW 1000 WE GW 1000 NWE 31 00426 Rev 10 20 12 DIMENSIONS GW 1000 WE GW 1000 NWE Gateway 59 mm 2 323 110 mm 4 331 45 mm 1 772 52 mm 2 047 135 mm 5 315 145 8 mm 5 744 ...

Page 21: ... ELECTRICAL IMPACT EN60204 1 is not mandatory this is because electrical safety is provided by the use of SELV and transformers according to standard EN60742 SAFETY AGAINST UNEXPECTED START UP OF ROTATING MOVING MACHINES If the application plant does not contain machines that can be harmful to the operator due to an unexpected start up the standard EN60204 1 is not applicable If such machines are ...

Page 22: ...ce Table 18 Accessories Part Number Description GW TCVR Replacement Terminal Covers Small Pack Quantity of 4 GW EXT TCVR Extended Terminal Covers Large Pack Quantity of 4 ANT REM Remote Antennas with adhesive magnetic foot for wireless communication 1 5 meter 4 9 feet cable length for remote mounting of the antenna Pack Quantity of 4 Ferrite Ring Part Number ZCAT3035 1330 BK Manufacture TDK GW ANT...

Page 23: ...a été approuvé par Innovation Sciences et Développement économique Canada pour fonctionner avec les types d antenne énumérés cidessous et ayant un gain admissible maximal Les types d antenne non inclus dans cette liste et dont le gain est supérieur au gain maximal indiqué pour tout type figurant sur la liste sont trictement interdits pour l exploitation de l émetteur Hub and Sensors MultiTech LoRa...

Page 24: ...vice TC500A N Commercial Thermostat Datasheet 31 00398M 1 Product data of the device TC500A N Commercial Thermostat Mounting Instructions 31 00399M 1 Describes the mechanical mounting and basic wiring of the device TC500A N Commercial Thermostat User Guide 31 00400M 1 Contains procedures for UI based functionalists of the device TC500A N Commercial Thermostat Quick Start Guide 31 00401M 1 Contains...

Reviews: