3
31-00426 | Rev.10-20
• When performing any work (installation, mounting,
start-up), all manufacturer instructions and in
particular the Installation and Commissioning
Instructions (EN1B-0205IE10) are to be observed.
• Gateway may be installed and mounted only by
authorized and trained personnel.
•
Rules regarding electrostatic discharge should be
followed.
•
If the GW-1000-WE/GW-1000-NWE gateway is
modified in any way, except by the manufacturer, all
warranties concerning operation and safety are
invalidated.
•
Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding.
•
Use only accessory equipment which comes from or has
been approved by Honeywell.
•
It is recommended that devices be kept at room
temperature for at least 24 hours before applying power.
This is to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
•
The GW-1000-WE/GW-1000-NWE gateway must be
installed in a manner (e.g., in a lockable cabinet)
ensuring that uncertified persons have no access to the
terminals.
•
Investigated according to United States Standard UL-
60730-1, UL-916, and UL60730-2-9.
•
Investigated according to Canadian National
Standard(s) C22.2, No. 205-M1983 (CNL-listed).
•
Do not open the GW-1000-WE/GW-1000-NWE
gateway, as it contains no user-serviceable parts inside.
•
CE declarations according to LVD Directive
2014/35/EU and EMC Directive 2014/30/EU.
•
Product standards are EN 60730-1 and EN 60730-2-9.
Professional Installation
•
This device must be professionally installed, this should
be noted on grantee.
•
To maintain compliance, only the antenna types that
have been tested shall be used, which listed in “Remote
Antenna Part Numbers” section on page 15. This device
requires a significant technology engineering expertise
towards understanding of the tools and relevant
technology, not readily available to average consumer.
Only a person professionally trained in the technology is
competent.
•
This device is not directly marketed or sold to general
public.
Safety Information as per EN60730-1
The GW-1000-WE/GW-1000-NWE gateway is intended for
residential, commercial, and light-industrial environments.
The GW-1000-WE/GW-1000-NWE gateway is an
independently mounted electronic control system with
fixed wiring.
The GW-1000-WE/GW-1000-NWE gateway is suitable for
mounting in fuse boxes conforming with standard
DIN43880, and having a slot height of max. 45 mm.
It is suitable for panel rail mounting on 35 mm standard
panel rail (both horizontal and vertical rail mounting
possible).
The GW-1000-WE/GW-1000-NWE gateway is used for the
purpose of building HVAC control and is suitable for use
only in non-safety controls for installation on or in
appliances.
Regulation (EC) No 1907/2006
According to Article 33 of REACH Regulation, be informed
that this product may contain components with lead (CAS:
7439-92-1) content above the threshold level of 0.1% by
weight.
Table 1. Safety Information as per EN60730-1
Electric Shock
Protection
PELV
Pollution Degree
Pollution Degree 2, suitable for use
in industrial environments.
Installation
Class 3
Overvoltage
Category
24 V-powered controls: Category I
Rated Impulse
Voltage
330 Vac for Category I (SELV)
Automatic
Action
Type1.Y
Software Class
Class A
Enclosure
IP20 according to EN-60529
Ball-pressure
Test
Temperature
>75 °C for all housing and plastic
parts
>125 °C in the case of devices
applied with voltage-carrying parts,
connectors, and terminals.
Electromagnetic
Interference
Tested at 230 Vac, with the
modules in normal condition.
System
Transformer
Europe: safety isolating
transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers
WEEE
WEEE Directive 2012/19/EC Waste
Electrical and Electronic Equipment
Directive
• At the end of the product life,
dispose of the packaging and
product in an appropriate recycling
center.
• Do not dispose of the device with
the usual domestic refuse.
• Do not burn the device.