GX-Series Control Panel Installation and Setup Guide
6-61
19 Fire {Not for UL installations}
The
Fire
function is continuously operational. When activated, a
FIRE
zone overrides the
Bell Delay
parameter and activates an instant alarm (
Bell
,
Strobe
and
Fire
). The keypad buzzer and control panel
horn output, if installed, emit an interrupted tone (one second on, 0.5 seconds OFF), easily distinguishable
from all other alarm conditions. Any valid code entry cancels the
Fire
activation.
20 Tamper
The
Tamper
function is continuously operational. When a
Tamper
zone is activated (1k
Ω
to 2k
Ω
), a tamper
alarm is generated; this requires to be reset by a code authorized for
Tamper Reset
- refer to option
51.7 =
PARAMETERS.Tamper Reset
. If a tamper condition (open or short circuit) occurs, a tamper alarm is also
generated.
21 Bell Tamper
This function is identical to the operation of the
Tamper
function but is dedicated to bells, sirens and other
modules or output devices requiring tamper protection.
22 Beam Pair
This function is only operational when two consecutively addressed zones programmed as
Beam Pair
are
open in the set condition; the activation is identical to the
Intruder
function. The system cannot set (arm) if
a single
Beam Pair
is open.
NOTE: Beam Pair zones must be consecutively addressed; the first Beam Pair zone must have an even number
address, the second Beam Pair must have the next address (an odd number). For example, valid Beam Pair
addresses are 1036 & 1037, 2018 & 2031 - in this case, RIO 202 has not been connected, therefore zone 2031 is
the next address to 2018.
23 Battery Low
This function is used to monitor the voltage output of a standby battery connected to a power supply. The
activation (
+
) and de-activation (–) of
Battery Low
zones is recorded in the event log.
24 Line Fail
The
Line Fail
function is used to monitor the communication line that a remote signaling device is
connected to for communications failure.
When the system is in the unset (disarmed) state, the first activation of a
Line Fail
zone causes a local
alarm and the message
COMMS FAILURE
is displayed, subsequent
Line Fail
activations do not sound
the local alarm; the only indication is the keypad display.
When the system is set (armed), activation of the
Line Fail
zone overrides the
Bell Delay
parameter; on
unsetting (disarming) the system a local alarm is generated and the keypad gives an indication that
Line
Fail
zone has activated. If an alarm condition occurs while the
Line Fail
is active, an instant full alarm is
generated.
If the
Line Fail
zone is active at the point of setting (arming), a warning message is displayed; the user can
choose to continue or abort the setting (arming) procedure. It is also possible to prevent the system setting
(arming) if the
Line Fail
is active by enabling the
Stop Set
parameter (option
51.18
).
25 AC Fail
This function is used to monitor a remote power supply. In the event of a power failure the
AC Fail
zone is
activated; the activation (
+
) and de-activation (–) of the zone is recorded in the event log.
26 Log
This zone type has no operational function; it is designed to record the activation of a zone in both the set
(armed) and unset (disarmed) state. The activation (
+
) and de-activation (–) of
Log
zones is recorded in the
event log.
27 Remote Access
This function is used to disable remote servicing of the GX-Series panel. When the
Remote Access
zone is
active the Remote Servicing software is prevented from gaining access to the GX-Series panel.
Summary of Contents for GX-48
Page 2: ......
Page 6: ...GX Series Control Panel Installation and Setup Guide iv ...
Page 26: ...GX Series Control Panel Installation and Setup Guide 2 18 ...
Page 32: ...GX Series Control Panel Installation and Setup Guide 3 6 ...
Page 40: ...GX Series Control Panel Installation and Setup Guide 4 8 ...
Page 46: ...GX Series Control Panel Installation and Setup Guide 5 6 ...
Page 184: ...GX Series Control Panel Installation and Setup Guide A 4 ...
Page 194: ...GX Series Control Panel Installation and Setup Guide C 2 ...
Page 200: ...GX Series Control Panel Installation and Setup Guide D 6 ...
Page 204: ...GX Series Control Panel Installation and Setup Guide F 2 ...
Page 207: ......