GX-Series Control Panel Installation and Setup Guide
6-63
Programming Example:
•
Zone 1014 = An on/off keyswitch programmed as
Exitguard.
•
Zone 1015 = A door contact programmed as
Security.
•
Output type
Link A
= An output wired to a local horn and programmed as
Link A
.
NOTE: Exit Guard zones do not omit zones open when the exit guard zone is activated, even if they are
subsequently closed.
Operation:
The
Security
door contact (
1015
) can be omitted at any time by operating the
Exitguard
keyswitch (1014). If the door (1015) is opened without first being omitted, then the
Link A
horn activates
and needs to be reset by operating the keyswitch (1014).
Link Source
Destination
1
Zone = 1014
Zone = 1015
2
Zone = 1015
Output = Link A
3
Zone = 1014
Output = Link A
Table 6-17. Exit Guard Zones
36 Mask
The
Mask
function is designed to be used with detectors capable of reporting that their field of view has
been blocked or masked. The
Mask
function is identical to the
Security
function, with the exception that
the
Mask
output is activated instead of
Security
.
NOTE: This zone type is independent from the mask zone state which can be detected for zones supporting the
masked feature.
37 Urgent
The
Urgent
function is continuously operational; it is identical to the
Intruder
function, with the exception
that it activates a full alarm condition (including the Intruder outputs) in any set (armed) or unset
(disarmed) condition.
38 PA Unset
This
PA Unset
function is identical to the
PA Silent
function, with the exception that it is only operational
when the system is unset (disarmed); the function is inactive when the group is set (armed).
39 Keyswitch Reset
The
Keyswitch Reset
function allows alarms to be cancelled and the system to rearm without unsetting
(disarming) the GX-Series. The type of reset authorization is determined by the
Keyswitch Level
(option
51.14
). The type required to reset
Intruder
,
PA
and
Tamper
alarms is determined by the
System Reset
,
Tamper Reset
and
PA Reset
parameters (option
51.06
,
51.07
and
51.22
) respectively.
This function is designed to permit a remote signal, for example REDCare’s Return Path Signaling feature,
to reset the system following an alarm condition.
40 Bell Fail
This zone type is intended for bells which have diagnostic capabilities and failure outputs. If activated, this
zone causes a fault condition.
41 Intr Low
This zone type assigns a low priority to a zone in the event of an intruder alarm. The event is logged as low
priority in the event log.
42 Intr High
This zone type assigns a high priority to a zone in the event of an intruder alarm. The event is logged as high
priority in the event log.
43 PSU Fault
This zone type triggers a general fault output and logs a PSU fault in the event log. The fault is signaled to
the ARC as
YP
when using SIA format and
314
when using CID format.
Summary of Contents for GX-48
Page 2: ......
Page 6: ...GX Series Control Panel Installation and Setup Guide iv ...
Page 26: ...GX Series Control Panel Installation and Setup Guide 2 18 ...
Page 32: ...GX Series Control Panel Installation and Setup Guide 3 6 ...
Page 40: ...GX Series Control Panel Installation and Setup Guide 4 8 ...
Page 46: ...GX Series Control Panel Installation and Setup Guide 5 6 ...
Page 184: ...GX Series Control Panel Installation and Setup Guide A 4 ...
Page 194: ...GX Series Control Panel Installation and Setup Guide C 2 ...
Page 200: ...GX Series Control Panel Installation and Setup Guide D 6 ...
Page 204: ...GX Series Control Panel Installation and Setup Guide F 2 ...
Page 207: ......