GX-Series Control Panel Installation and Setup Guide
6-121
The GX-Series control panel provides programming of timer schedules on a weekly basis. Each event
corresponds to an ON or an OFF time. The state of the schedule is ON or OFF depending on the last event
that was reached.
Timers can be assigned to:
•
Individual users to disable them
•
Individual doors to lock them
•
Individual groups for autoset
•
Outputs for automatic activation.
NOTE: The ON period is the secure period for a particular schedule when users will be unable to gain access to
allocated areas and the Autoset (armed) and Lockout features for allocated groups are enabled.
The Timers menu Structure is as follows:
65.1 = Weekly Schedule
A weekly schedule consists of a selection of daily time programs for each day of the week. The state of the
weekly schedule is ON or OFF depending on the last event that was reached. Up to 67 weekly schedules
with 28 time slots are available for programming depending on panel variant The weekly schedules are used
to control various panel features:
•
Auto setting/arming
•
Lockout times
•
User access times
•
Timer Outputs
1 = Name
A maximum 12 character alpha-numeric name can be entered here for a weekly schedule.
2 = Status
The status of the each of the timers is shown here whether
0 = OFF
or
1 = ON
. To change the status
press the
A>
or
<B
key or press
1
to select
ON
or
2
to select
OFF.
3 = Events
This option programs the weekly timer events with Day (Mon-Sun) and ON/OFF times.
NOTE: The number of weekly timer events is dependent on panel variant.
Programming Timer Events
1. Enter the Weekly Schedule menu. The first timer is displayed.
2. Go
to
3 = Events
and press enter. The programmed status (if any) of the first timer is displayed.
3. If the timer has not been programmed then the following window appears on the keypad:
GX-086-V0
4. To enter a new timer program for W01 do the following:
•
Press
ent
to select the timer.
•
Press the
A>
or
<B
keys to select the day (MON to SUN).
•
Press the
#
key to select the status
ON
or
OFF.
•
Press the number keys (0-9) to select the first time (4 digit 24 hour format) on the top row.
•
Press
ent
to accept the programming. The following typical window is displayed:
GX-087-V0
5. To program the OFF time on the bottom row repeat step 4. The following typical window is
displayed:
Summary of Contents for GX-48
Page 2: ......
Page 6: ...GX Series Control Panel Installation and Setup Guide iv ...
Page 26: ...GX Series Control Panel Installation and Setup Guide 2 18 ...
Page 32: ...GX Series Control Panel Installation and Setup Guide 3 6 ...
Page 40: ...GX Series Control Panel Installation and Setup Guide 4 8 ...
Page 46: ...GX Series Control Panel Installation and Setup Guide 5 6 ...
Page 184: ...GX Series Control Panel Installation and Setup Guide A 4 ...
Page 194: ...GX Series Control Panel Installation and Setup Guide C 2 ...
Page 200: ...GX Series Control Panel Installation and Setup Guide D 6 ...
Page 204: ...GX Series Control Panel Installation and Setup Guide F 2 ...
Page 207: ......