GX-Series Control Panel Installation and Setup Guide
2-13
When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 328 feet (100 m) in this
configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 1640 feet (500 m) in all other
configurations.
Option 02 - 1k
Option 04 – 2.2k
Option 06 – 4.7k
Option 08 – 5.6k
Option 10 -1k Fault
Tamper S/C
0 - 800 0 – 1800
0 – 3700
0 – 1400
0 - 800
Low Res
800 – 900
1800 – 2000
3700 – 4200
1400 – 2800
800 - 900
Normal
900 – 1200
2000 – 2500
4200 – 5500
2800 – 8400
900 - 1200
High Res
1200 – 1300
2500 – 2700
5500 – 6500
8400 – 9800
1200 - 1300
Fault - - - -
1300
-
4500
Masked
1300 – 12000
2700 – 12000
6500 – 19000
9800 – 19000
4500 - 19000
Open
12000 – infinity
12000 – infinity
19000 – infinity
19000 – infinity
19000 – infinity
Table 2-7. End of Line Zone Resistance and Conditions
Option 10 - 1k Fault End-Of-Line
The wiring in Figure 2-14 should be used if the mode is end-of-line. Fault and mask indications can only be
signaled if the detector has separate fault and mask indications.
Zone
Tamper N/C
1k
Alarm N/C
Fault N/C
3k
12k
Anti-mask N/C
GX-014-V2
328 ft (100 m)
Figure 2-14. Option 10 - End of Line Zone/Detector wiring
When this wiring mode is employed, only one detector which can report fault conditions should be connected
to the zone. A maximum of two detectors or contacts of any type should be connected to a zone when this
mode is selected. It is recommended that zone cable lengths are kept below 100m in this configuration.
NOTE: The recommended maximum cable run from a zone to a detector is 1640 feet (500 m) in all other
configurations.
Wiring Multiple Detectors
Multiple detectors can be wired into a single zone when using preset 1 as shown in Figure 2-15. The
maximum number of detectors that can be connected to a single zone is ten.
Zone
Alarm
Alarm
Alarm
Alarm
N/C
N/C
N/C
N/C
N/C TAMP
1k
1k
1k
1k
1k
1%
1%
1%
1%
1%
N/C
(10 max)
GX-015-V1
1640 ft (500 m)
Figure 2-15. Zone to Multiple Detector Wiring
Summary of Contents for GX-48
Page 2: ......
Page 6: ...GX Series Control Panel Installation and Setup Guide iv ...
Page 26: ...GX Series Control Panel Installation and Setup Guide 2 18 ...
Page 32: ...GX Series Control Panel Installation and Setup Guide 3 6 ...
Page 40: ...GX Series Control Panel Installation and Setup Guide 4 8 ...
Page 46: ...GX Series Control Panel Installation and Setup Guide 5 6 ...
Page 184: ...GX Series Control Panel Installation and Setup Guide A 4 ...
Page 194: ...GX Series Control Panel Installation and Setup Guide C 2 ...
Page 200: ...GX Series Control Panel Installation and Setup Guide D 6 ...
Page 204: ...GX Series Control Panel Installation and Setup Guide F 2 ...
Page 207: ......