GX-Series Control Panel Installation and Setup Guide
6-50
2 = System Reset:
Sent when the system is fully reset.
57 = Bell Extend
If enabled, this parameter extends the bell time if the system cannot rearm. For example, if the zone is still
open and cannot be omitted. The bell time can be extended up to 30 minutes maximum. The Default is 0, no
extension.
58 = Power Alarm
If enabled, this parameter allows the Bells, Strobe and Horn outputs to activate when there is an AC fail
and the system is set (armed). The default is 0.
59 = Part Tone
When enabled, this parameter changes the setting tone for a part set (part arm). The new tone is
on 2 secs,
off 0.1 sec.
60 = NOT USED
61 = Activity Mon.
This parameter allows zone activity to be checked. If zones programmed for zone activity checks are not
activated within the programmed time period and/or number of set/unset (arm/disarm) cycles a zone masked
fault is indicated at the panel. Six different combinations of check criteria are available for each zone.
Each criteria type can be programmed to check the number of days, the set/unset (arm/disarm) cycles or
both. Default value is both.
1 = Mode
The mode can be set to one of three options: Max Period, Max Unsets or Either.
2 = MAX Period
The time period that zone activity is checked can be set to between 1 and 28 days. Default is 14 days.
3 = MAX Unsets
This is the number of programmable set/unset (arm/disarm) cycles that must take place before a zone
masked fault is indicated at the panel. The number of set/unset (arm/disarm) cycles can be programmed
from 1 - 10. The default is 7.
62 = Lockout
This parameter prevents code guessing on the GX-Series system.
1=Lockout
This parameter determines the number of invalid code attempts, which can be tried before keypad
lockout occurs. Keypad lockout prevents any entry via all keypads associated to the groups assigned to
the keypad where the invalid attempts were made. The lockout lasts for 90 seconds. Each subsequent
invalid attempt causes a further 90 second lockout to occur. Entry of a valid code will reset the lockout
counter. Lockout can be programmed between 0 and 10. Default is 6. Setting to 0 disables the function.
2=Tamper
This parameter determines the number of invalid code attempts, which can be tried before system
tamper occurs. Lockout tamper can be programmed between 0 and 21. Default is 15. Setting to 0
disables the function.
63 = Banner Alerts {Required for UL installations}
This parameter determines whether system alerts are displayed on the GX-Series keypad banner. If enabled
system events will be indicated on the display. The default value for this parameter is disabled.
64 = Set Override
This parameter determines the type of user that can override specific fault events to set (arm) the system.
The default values are shown in the following table:
Summary of Contents for GX-48
Page 2: ......
Page 6: ...GX Series Control Panel Installation and Setup Guide iv ...
Page 26: ...GX Series Control Panel Installation and Setup Guide 2 18 ...
Page 32: ...GX Series Control Panel Installation and Setup Guide 3 6 ...
Page 40: ...GX Series Control Panel Installation and Setup Guide 4 8 ...
Page 46: ...GX Series Control Panel Installation and Setup Guide 5 6 ...
Page 184: ...GX Series Control Panel Installation and Setup Guide A 4 ...
Page 194: ...GX Series Control Panel Installation and Setup Guide C 2 ...
Page 200: ...GX Series Control Panel Installation and Setup Guide D 6 ...
Page 204: ...GX Series Control Panel Installation and Setup Guide F 2 ...
Page 207: ......