5 Specifications
Input power:
100-240 VAC, 50/60 Hz
24 VDC
DC output power:
15 watts (internal supply) or
50 watts (internal supply)
Relay output rating:
5A, 28 VDC or 250 VAC (resistive load)
Optional relay output rating
5A, 28 VDC or 250 VAC (resistive load)
Optional milliamp loop
output
10 bit 4-20mA output. Maximum load 750 ohms
with nominal 24 Vdc
Communication:
RS232 Modbus
Length of communication
lines:
Operating environment:
Industrial
Operating temperature
range:
-25 to 50ºC (-13ºF to 122ºF)
Operating humidity range:
0 to 90% RH non-condensing
Operating altitude:
2000m (6562 ft)
Audible alarm:
100 dB
Display:
128 x 64, backlight graphic LCD
Visual Indicators:
6 LED status indicators
Pollution degree:
N4: 3
Enclosure (N4):
NEMA 4X, Div. 2, Groups A,B,C,D, Category II
Enclosure (XP):
NEMA 7, Div. 1 & 2, Groups B,C,D
Dimensions (H x W x D):
N4: 10.32” x 8.92” x 3.17” (23.62 x 22.66 x 8.05cm)
XP: 15.10” x 13” x 6.25” (36.2 x 33 x 15.88cm)
Enclosure
NEMA 4 painted carbon steel
Enclosure
NEMA4X SS316
Enclosure
NEMA4X Polycarbonate
Weight:
N4: 2.27 Kg XP: 18.14 Kg
Certifications:
CSA C22.2 No. 1010-1, ISA S82.02
CSA C22.2 No 152 (for combustibles using mA
input)
UL 1604/C22.2 No. 213 (NEMA 4X = Div 2, Gr A,
B, C, D; NEMA 7 = Div 1, Gr , B, C, D
EN55011 & EN61000 (CE mark))
Summary of Contents for HA40
Page 6: ...HA40 4 Channel Controller HA40 Technical Manual 1 1 1 General Description ...
Page 11: ...HA40 4 Channel Controller HA40 Technical Manual 2 1 2 Operation ...
Page 21: ...HA40 4 Channel Controller HA40 Technical Manual 2 11 ...
Page 22: ...HA40 4 Channel Controller HA40 Technical Manual 3 1 3 Motherboard Interface PCB ...
Page 31: ...HA40 4 Channel Controller HA40 Technical Manual 4 1 4 Enclosures ...
Page 34: ...HA40 4 Channel Controller HA40 Technical Manual 5 1 5 Parts List ...
Page 36: ...HA40 4 Channel Controller HA40 Technical Manual 6 1 6 Specifications ...
Page 38: ...HA40 4 Channel Controller HA40 Technical Manual 7 1 7 Warranty ...